Safety regulations for battery energy storage systems (2026)

  • CEA
  • 27 March 2026
  • F. No. CEA-PS-16/1/2021-CEI Division
StorageBatteriesEMS

What it says

The CEA (Measures relating to Safety and Electric Supply) Amendment Regulations, 2026 add a chapter on BESS safety. Published in the Gazette on 30 March 2026, in force from 1 April 2027.

Key provisions

  1. Two-fault tolerance against overcharge, over-discharge, short circuit and operation outside temperature limits.
  2. The BMS must monitor and record voltage, temperature and thermal runaway at cell, module and rack level, and stop charging and discharging above the maker's temperature limit.
  3. Containers need explosion protection, forced ventilation, gas, smoke, heat and flame detection, and automatic fire suppression.
  4. Sites need fencing of at least 1.8 m, CCTV, alarms, and automatic and manual emergency stops.
  5. An independent fire safety audit is due within three months of commencement, reported to the Electrical Inspector.
  6. Regulations 122(A) to 122(M) apply above 650 V; systems at 650 V and below must meet the relevant standards.