StorageEMSGrid
What it says
Secondary and tertiary reserve services procured through the market, open to energy storage and demand response. Most provisions in force from 5 December 2022.
Key provisions
- Generators, energy storage and demand response can take part, alone or aggregated, on inter-state or intra-state networks.
- Secondary reserve providers need two-way communication with the RLDC, metering, SCADA telemetry and at least 1 MW.
- Secondary reserve must respond within 30 seconds, reach full capacity within 15 minutes and hold it for 30 minutes.
- Tertiary reserve must deliver within 15 minutes and hold for at least 60 minutes.
- Reserves are activated by the NLDC through AGC or despatch signals and settled through the deviation and ancillary services pool.