What it says
A new grid code for planning, connection, commissioning, scheduling and operation, treating energy storage as its own class of grid user. In force from 1 October 2023.
Key provisions
- A standalone storage trial run is one full charge-discharge cycle with metering, telemetry and protection in service.
- Storage must certify CEA connectivity compliance and pass tests for MW/MWh capability, frequency response and ramping.
- A solar trial run needs at least four hours of power flow with the plant controller, telemetry and protection in service.
- All RE plants and storage must control active-power injection as CEA standards require.
- RE and storage at ISTS substations may appoint a QCA for scheduling; RLDCs forecast wind, solar and storage output.