1250 kVA DG sets (diesel and gas generator sets) in India

4 products from 3 companies, side by side. All 122 products in DG sets · Listed A–Z, not ranked · Reviewed November 2026

1250 kVA sets back up very large industrial plants, data centres and airports. They use large V-type engines; check the rating basis, fuel consumption and the space and foundation needed.

1250 kVA compared

A–Z by company, not ranked · NA: not published by the maker

FieldKirloskar Oil EnginesKG1-1250WS1250 kVA Diesel GeneratorKirloskar Oil EnginesOptiprime 1250Optiprime 1250 kVA Diesel GensetOjus Power and Technologies1250 kVADiesel generator setSudhir PowerCS D5P seriesCummins-powered silent diesel gensets (2023 brochure)
Output
Rating 1250 kVA1250 kVA1250 kVA7.5–2250 kVA
Power output 1000 kWe1000 kWeNANA
Printed ratings 1250 kVA1250 kVANA7.5, 10, 15, 20, 25, 30, 35, 40, 50, 62.5, 82.5, 100, 125, 140, 160, 180, 200, 225, 250, 275, 300, 320, 380, 400, 500, 600, 625, 650, 750, 810, 910, 1010, 1250, 1500, 1800, 2000, 2250 kVA
Rating basis PrimePrimeNAPrime
Output voltage 415 (3ɸ)415 (3ɸ)415NA
Frequency 50 Hz50 Hz50 HzNA
Power factor 0.80.80.8NA
Phase 3-phase3-phase3-phaseNA
Build
Fuel DieselDieselDieselNA
Engine 12K4300-E1DV10ETA 4G2Baudouin 12M33D1210E200X1.3TAA-G1, X1.3TAA-G7
Alternator NANAStamford HCKI634ZNA
Enclosure AcousticNANAAcoustic
Dimensions (L × W × H) 8500 × 2560 × 3120 mm (axes not stated)NA8004 × 2500 × 2859 mm (axes not stated)10450 × 3500 × 3800 mm (axes not stated)
Fuel tank capacity NANA990NA
Weight 18250 kgNA13500 kgNA
Certification
CPCB IV+ YesYesNANA
Certifications and standards ISO 8528NAISO 8528-5NA
Performance
Governing class G3NAG3 as per ISO 8528-5NA
Fuel consumption NANA187.2 L/h at 75% loadNA
Noise level NA<75 DBANA75 dBA at 1 m
Controls
Controller NANANAPS0600/1/2 (15-1010 kVA); PCC 3201 (1250-3750 kVA)
Support
Warranty NANA2 years or 5000 operational hours from the date of commissioningNA
Source
NoteWeight is the dry weight (maximum) printed on the sheet.
Model codeNANANACS 7.5 D5P to CS 2250 D5P
DatasheetSpec page of Kirloskar Oil Engines KG1-1250WS (opens the maker's site)Spec page of Kirloskar Oil Engines Optiprime 1250 (opens the maker's site)Datasheet (PDF) of Ojus Power and Technologies 1250 kVA (opens the maker's site)Datasheet (PDF) of Sudhir Power CS D5P series (opens the maker's site)
CheckedFigures compared with the maker's sheetNovember 2026November 2026November 2026November 2026
DetailsDetails of Kirloskar Oil Engines KG1-1250WSDetails of Kirloskar Oil Engines Optiprime 1250Details of Ojus Power and Technologies 1250 kVADetails of Sudhir Power CS D5P series

Values as each maker prints them on its own datasheet or spec page, linked in the Datasheet row at the foot of the table; Checked is the date we compared these figures with the maker's sheet. Each rating is shown with the basis its maker prints (prime, standby or not stated); prime and standby figures are not the same and shouldn't be compared directly. A range covers the variants on one sheet. Nothing here is tested by Ingro Energy, and the order is alphabetical by company.

What differs between them

Counted from the 4 products above, as printed.

  • Rating: 7.5 to 2250 kVA as printed (ranges included)
  • Power output: 1000 kWe; 2 of 4 publish it
  • Rating basis: Prime; 3 of 4 publish it
  • Fuel: Diesel; 3 of 4 publish it
  • CPCB IV+: 2 of 4; 2 not published
  • Output voltage: 415 (3ɸ) on 2, 415 on 1; 1 not published
  • Frequency: 50 Hz; 3 of 4 publish it
  • Power factor: 0.8; 3 of 4 publish it
  • Governing class: 2 of 4 publish it; values in the table
  • Phase: 3 of 4 publish a list; 3-phase on 3
  • Engine: 4 of 4 publish it; values in the table
  • Alternator: Stamford HCKI634Z; 1 of 4 publishes it
  • Enclosure: Acoustic; 2 of 4 publish it
  • Fuel consumption: 187.2 L/h at 75% load; 1 of 4 publishes it
  • Noise level: <75 DBA on 1, 75 dBA at 1 m on 1; 2 not published
  • Controller: PS0600/1/2 (15-1010 kVA); PCC 3201 (1250-3750 kVA); 1 of 4 publishes it
  • Dimensions (L × W × H): 3 of 4 publish it; values in the table
  • Fuel tank capacity: 990; 1 of 4 publishes it
  • Weight: 13500 to 18250 kg as printed; 2 not published
  • Warranty: 2 years or 5000 operational hours from the date of commissioning; 1 of 4 publishes it
  • Certifications and standards: 2 of 4 publish a list

Questions about 1250 kVA DG sets (diesel and gas generator sets)

Which companies make 1250 kVA DG sets (diesel and gas generator sets) in India?
3 companies list 4 products at this size: Kirloskar Oil Engines (KG1-1250WS, Optiprime 1250); Ojus Power and Technologies (1250 kVA); Sudhir Power (CS D5P series). They are listed A–Z by company, not ranked.
How do these 1250 kVA DG sets (diesel and gas generator sets) differ?
Rating: 7.5 to 2250 kVA as printed (ranges included). Power output: 1000 kWe; 2 of 4 publish it. Rating basis: Prime; 3 of 4 publish it. Fuel: Diesel; 3 of 4 publish it. Counted from the 4 products as each maker prints them.
Where do these figures come from?
From each maker's own datasheet or spec page, checked November 2026. Products printed within ±3% of 1250 kVA are grouped on this page, each showing its own printed figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with the companies listed.

Not sure what to buy? Ask us what's compatible and what size fits your site.