As printed in the datasheet, checked November 2026 (the date we compared these figures with the maker's sheet). NA means not published.
Rating
Rated energy Rated energy: How much electricity it stores when full. A 261 kWh cabinet can supply 125 kW for about 2 hours. Size it against the hours of backup you need, or the load you want to shift.
522.496 kWh
Rated power Rated power: The most it can charge or discharge at once. It has to cover the load you want to run from the battery. Battery-only blocks, sold without their inverter (PCS), often print no kW figure.
n/a (no PCS)
Charge/discharge rate C-rate / P-rate (0.5P): How fast a battery charges or discharges compared with its size. 0.5P means full power is half the energy rating: 5000 kWh at 0.5P gives 2500 kW, for about 2 hours. 1P empties in about 1 hour.
0.5 P
Duration Duration: How many hours the system can deliver its rated power from full. Worked out by us, not printed by the maker: rated energy ÷ rated power, or 1 ÷ the printed charge/discharge rate (0.5P = 2 h). Shown only when the sheet prints one energy and one power figure, or a rate.
2 h
PCS included PCS included: The PCS (power conversion system) is the battery's inverter: it turns the battery's DC into the AC your site uses. "No" means a battery-only block, and the PCS is bought and wired separately.
No
Cooling Cooling: How the cells are kept at the right temperature. Liquid cooling keeps cells more even and suits hot sites and heavy daily use; air cooling is simpler and common in smaller systems.
Liquid
Battery
Cell capacity Cell capacity: The size of each battery cell. 280 and 314 Ah are today's mainstream; cells of 500 Ah and more are newer. It tells you the cell generation, not how good the system is.
314 Ah
Chemistry Chemistry: The battery type. LFP (lithium iron phosphate) is the standard for stationary storage: it handles heat better and lasts longer than NMC.
LFP
DC voltage range DC voltage range: The battery's voltage from empty to full. The PCS must work across this window, which matters when the battery and the PCS come from different makers.
715–936 V
Cycle life DoD (depth of discharge): How much of the battery's capacity a cycle uses. Cycle-life claims depend on it: 6000 cycles at 80% DoD is not the same as at 100%.
NA
Electrical
AC voltage AC voltage: The voltage at the system's AC output. Cabinets usually output 380 or 400 V three-phase, close to the 415 V supply in most Indian buildings; check the PCS covers your site's voltage, or a transformer goes in between.
n/a (no PCS)
AC frequency AC frequency: India's grid runs at 50 Hz. A model listed only at 60 Hz is a variant for other markets.
n/a (no PCS)
Round-trip efficiency RTE (round-trip efficiency): The share of energy you get back out of what you put in: 90% means 10 kWh lost per 100 kWh stored. Check what it is measured on (DC side or AC system); makers differ.
NA
Efficiency measured Efficiency measured: Where the efficiency was measured. A DC-side figure leaves out the inverter's losses, so it looks higher than an AC figure; an AC figure that includes auxiliary loads (cooling, controls) is closest to what you actually get back. Compare like with like.
NA
Physical
Size (mm) Size (mm): Outside size, W × D × H or as printed. Leave room around it for the doors to open, for cabling, for air to flow and for service access.
2000 × 1400 × 2190 mm (axes not stated)
Weight Weight: What the plinth or floor must take. An outdoor cabinet of about 250 kWh weighs 2 to 3 tonnes, and placing it usually needs a forklift or crane.
up to 5100 kg
Enclosure rating Enclosure rating: How well the enclosure keeps out dust and water (IP code: first digit dust, second digit water). IP54 or IP55 is usual for outdoor units; some sheets print a US NEMA type instead.
IP54
Environment
Operating temperature Operating temperature: The outdoor (ambient) temperatures it is built to run in. Check the top end against your site's summer peak (Indian summers often pass 45 °C); output may be reduced (derated) near the limit.
-30–55 °C
Max altitude Max altitude: Thin air cools less well. Above this height the output is reduced, or the warranty may not apply. Most Indian sites are well below 2000 m; it matters mainly in the hill states.
3000 m
Noise at 1 m Noise at 1 m: How loud it is one metre away, mostly from the cooling fans. It matters near offices, homes and the site boundary.
NA
Safety
Fire suppression Fire suppression: What the system does if a cell overheats: gas, smoke and heat detectors raise the alarm, gas or aerosol puts out a fire, and vents or panels let explosive gas out safely. Some add a water spray or sprinkler line.
Aerosol, water
Certifications Certifications: The safety and grid standards it is tested to. IEC 62619 covers battery safety, IEC 62933 and UL 9540 the whole storage system, UL 9540A how a fire spreads between cells and racks, and UN 38.3 safe transport. In India, also ask which BIS (IS) certifications the cells and the PCS carry.
MC-L430-2H2Liquid-cooled C&I AC BESS cabinet, 200 kW / 430 kWh
MC-L430-BC-2Liquid-cooled C&I DC battery cabinet, 430 kWh
MC-L522-2H3Liquid-cooled C&I AC BESS cabinet, 250 kW / 522 kWh
MS-G(S)215-2H3Air-cooled C&I ESS cabinet, 100 kW / 215 kWh (GS version with PV input)
Deye MC-L522-BC-3, in short
The Deye MC-L522-BC-3 is a cabinet BESS rated 514 kWh, with cooling Liquid and PCS included: no. 3 other cabinet BESS at 514 kWh are listed, from 3 makers. Deye has 4 other cabinet BESS on this site.
What are the main specifications of the Deye MC-L522-BC-3?
Rated 514 kWh; Cooling Liquid; PCS included: no. As printed on Deye's datasheet (checked November 2026); the full list is on this page.
Where can I find the Deye MC-L522-BC-3 datasheet?
Deye publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
What are the alternatives to the Deye MC-L522-BC-3?
Other 514 kWh cabinet BESS sold in India include Ecosolex M125G522A, Sungrow PowerStack 255CS 125kW/514kWh and Deye MC-L522-2H3.
Who makes the Deye MC-L522-BC-3?
Deye. It has 5 cabinet BESS on this site, including this one.
Spot a wrong or outdated figure?Report a correction and we'll check it against the maker's current sheet.
Values as Deye prints them in the linked datasheet; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with Deye. Product and company names are trademarks of their owners, used only to identify the product.