Hitachi Energy India PCS WD4

Listed A–Z, not ranked · Reviewed November 2026

Power Conversion System, 6 MVA power solution for BESS (liquid cooled, up to 1500 Vdc) · PCS by Hitachi Energy India

As printed in the datasheet, checked November 2026 (the date we compared these figures with the maker's sheet). NA means not published.

AC side

Rated power
4839–5118 kW
Printed ratings
4839, 4980, 5118 kW
Nominal AC voltage
690–730 V
Grid frequency
NA

DC side

DC voltage range
987–1500 V
Max DC current
NA

Performance

Max efficiency
98.82 %

Build

Type
NA
Cooling
Liquid
Ingress protection
IP65
Operating temperature
-25–55 °C
Weight
about 8000 kg
MV transformer built in
No
Communication
NA

Grid functions

Off-grid / black start
Yes
Grid-forming
Yes

Certification

Certifications
IEC 62477, IEC 62109-1, IEC 62109-2, IEC 61000-3-4, IEC 61000-3-11, IEC 61000-3-12, IEC 61000-6-4, CE Marking
Size:
4839 kW
, 5000 kW
Model code:
PCS-WD4-V690, PCS-WD4-V710, PCS-WD4-V730
Checked:
November 2026, against the datasheet

Note

Rated at 50 °C; 5376–5688 kW at 35 °C.

Full datasheet

Every row the maker prints, copied as written, read 2026-11-15.

Overview

Product
Power Conversion System (PCS) WD46 MVA power solution
Models
PCS-WD4-V690; PCS-WD4-V710; PCS-WD4-V730
Description
Bidirectional plug and play converter, optimized for BESS and DC-coupled hybrid systems integration into complex electrical grids, and compatible with leading battery manufacturers.Fast response and advanced active power management for highly demanding environments (e.g. ramp rate, frequency response).Flexible DC bus connection ensuring efficient project sizing, especially important for large-scale storage projects.Seamless integration between Hitachi Energy’s power plant controller (PPC) and the battery management system (BMS) from the battery manufacturer.PCS is a high power density power conversion system for utility-scale battery energy storage systems (up to 1500 VDC). It is optimized for BESS integration into complex electrical grids and is based on our best-in-class liquid cooled power conversion platform, enabling greater scalability and efficiency.(hitachienergy.com)

DC side

SoC voltage range at full power (Vdc)
PCS-WD4-V690: 987-1500; PCS-WD4-V710: 1016-1500; PCS-WD4-V730: 1044-1500
Max. DC voltage (Vdc)
1550
Max. input current (A)
3 x 2000
Withstand current (A)
250 kA maximum available fault current, 5.58 MA2s pre-arcing energy (without internal fuse); 250 kA maximum available fault current (with internal fuse); Time constant τ = L/R (tau) of the DC circuit must be between 0,3 ms and 3 ms
Number of DC inputs
3

AC side

AC output power at 35 °C (kVA/kW)
PCS-WD4-V690: 5376; PCS-WD4-V710: 5532; PCS-WD4-V730: 5688
AC output power at 50 °C (kVA/kW)
PCS-WD4-V690: 4839; PCS-WD4-V710: 4980; PCS-WD4-V730: 5118
Nominal AC voltage (V)
PCS-WD4-V690: 690; PCS-WD4-V710: 710; PCS-WD4-V730: 730
Max. AC current at 35 °C
3 x 1500
Power factor
Adjustable
Current harmonic distortion (THDi)
<3%

Efficiency

Max. / Euroeta / CEC efficiency (%)
PCS-WD4-V690: 98.8 / 98.41 / 98.4; PCS-WD4-V710: 98.82 / 98.44 / 98.44; PCS-WD4-V730: 98.82 / 98.46 / 98.46

Protection

DC protection and disconnection
DC load break switchOptional
AC protection and disconnection
AC circuit breaker
Overvoltage protection
Class II / type 2 (optional class I + II / type 1)
Ground fault / insulation monitoring
YesYes

Environment

Operating temperature
From -13ºF to 131ºF (-25ºC to 55ºC), derating < 5ºF (-15ºC) and >95ºF (35ºC)
Storage temperature
5ºF / 149ºF (-15ºC / 65ºC) coolant filled; -13ºF / 149ºF (-25ºC / 65ºC) without coolant
Relative humidity
100%
Storage humidity
From 5% to 85%
Max. altitude
4000 masl, derating >1000masl
Ingress protection
IP65
Cooling
Liquid cooling system

Physical

Dimensions (W × D × H)
6977 x 1100 x 2535 mm
Weight
~8 tn

Certifications

Certifications and standards
IEC 62477; IEC 62109-1, IEC 62109-2, IEC62109; IEC 61000-3-4, IEC 61000-3-11, IEC 61000-3-12, IEC 61000-6-4; CE Marking; Grid code certificates available on request

Features

Features
System Strength; Synthetic Inertia; Grid Forming; Power Quality; Black StartAbility to perform in high altitude mountain regions up to 4000 MASL.Internal electronics and components are coated for resistance to corrosive, salt-intensive conditions.Sealing elements and standard enclosures with IP65 rated protection against rain and moisture.Liquid cooling system combined with filters and enhanced protection prevents dust ingress.Low temperature and reduced noise kits (optional)Robust design for maximum power in extreme ambient conditions; Multilevel coordinated control ensures fast dynamic response; Advanced control to support grid forming; Full power rating up to 1500 VDC ensures efficient project sizing(hitachienergy.com)Load leveling; Frequency regulation; Capacity firming; Peak shaving; Voltage support; Islanding; Black start; Grid inertia(hitachienergy.com)Effective operating conditions in remote high-altitude; Coating on internal components and electronics to resist corrosive saline conditions; Sealing elements and standard IP65 enclosure; Protection against rain and humidity(hitachienergy.com)

More PCS from Hitachi Energy India

  • PCS WD3Power Conversion System, power conversion station for utility-scale BESS (up to 1500 Vdc)

Hitachi Energy India PCS WD4, in short

The Hitachi Energy India PCS WD4 is a PCS rated 4839 kW, with max efficiency 98.82%, cooling Liquid and MV transformer built in: no. Its max efficiency (98.82%) is above the median of the 45 PCS listed (98.7%). Hitachi Energy India has 1 other PCS on this site.

Questions about the Hitachi Energy India PCS WD4

What are the main specifications of the Hitachi Energy India PCS WD4?
Rated 4839 kW; Max efficiency 98.82%; Cooling Liquid; MV transformer built in: no. As printed on Hitachi Energy India's datasheet (checked November 2026); the full list is on this page.
Where can I find the Hitachi Energy India PCS WD4 datasheet?
Hitachi Energy India publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
Who makes the Hitachi Energy India PCS WD4?
Hitachi Energy India, with its head office in Bengaluru. It has 2 PCS on this site, including this one.

Spot a wrong or outdated figure? Report a correction and we'll check it against the maker's current sheet.

Values as Hitachi Energy India prints them in the linked datasheet; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with Hitachi Energy India. Product and company names are trademarks of their owners, used only to identify the product.

Not sure what to buy? Ask us what's compatible and what size fits your site.