As printed in the datasheet, checked November 2026 (the date we compared these figures with the maker's sheet). NA means not published.
AC side
Rated power Rated power: The AC power the PCS can deliver when discharging the battery, or take in when charging it. Datasheets often print kVA, which equals kW at a power factor of 1. Output usually drops in hot weather, so check the rating at your site's summer temperature.
215 kW
Printed ratings Printed ratings: Every power size the maker lists for this series. Choose from these; sizes in between are not offered unless the maker says so.
215 kW
Nominal AC voltage Nominal AC voltage: The voltage at the converter's AC terminals. A 400 V unit can usually join a factory's 415 V three-phase supply directly; 480–800 V units feed a step-up transformer to an 11 kV, 33 kV or higher connection. With a built-in MV transformer, this is still the converter-side voltage.
690 V
Grid frequency Grid frequency: India's grid runs at 50 Hz. A model listed only at 60 Hz is a variant for other markets; 50/60 means it can be set for either.
50/60
DC side
DC voltage range DC voltage range: The battery voltage window the PCS can work with. The battery's voltage from empty to full must sit inside it, which matters when the battery and the PCS come from different makers. Most large systems today run up to 1500 V DC.
1000–1500 V
Max DC current Max DC current: The most current the PCS can draw from or send into the battery. DC cables, fuses and the battery's own current limit must be sized for at least this.
209 A
Performance
Max efficiency Max efficiency: Share of input power that comes out as useful output at the best operating point; the rest is lost as heat. It is a peak figure, so losses are higher at low load. With a built-in MV transformer, it includes the transformer's losses.
NA
Build
Type Type: How the maker describes the build: Central (one large converter per battery block), String (several smaller converters, each on its own battery rack, so one fault takes out less capacity), Cabinet (a self-contained cabinet unit) or Modular (built from power modules that can be swapped or added).
String
Cooling Cooling: How the power electronics get rid of their heat. Air cooling uses fans and filters that need regular cleaning on dusty sites; liquid cooling pumps coolant through the unit, handles heat well in a compact box, and adds a coolant loop to maintain.
Liquid
Ingress protection Ingress protection: How well the enclosure keeps out dust and water (IP code: first digit dust, second digit water). IP54 to IP66 is usual for outdoor units. NEMA types (3R, 4X) are the North American system for outdoor enclosures; 4X also resists corrosion.
IP66
Operating temperature Operating temperature: The ambient range it is built to run in. Check the top end against your site's summer peak (Indian summers often pass 45 °C); output may be reduced (derated) near the limit.
-40–60 °C
Weight Weight: What the plinth or foundation, the crane or forklift and the transport must take. A small cabinet unit can be a few hundred kilograms; a station with a built-in MV transformer weighs many tonnes.
up to 80 kg
MV transformer built in MV transformer built in: MV means medium voltage, such as 11 kV or 33 kV. "Yes" means a power station or skid: the PCS and a step-up transformer come as one factory-built unit (no battery), and its efficiency and weight cover the whole station. "No" means the converter alone, with the transformer bought separately.
No
Communication Communication: The ways the PCS talks to the battery management system (BMS), the plant controller and SCADA (the site's monitoring and control system). Modbus, over an RS485 serial cable (RTU) or Ethernet (TCP), is common; CAN is often used to the BMS; IEC 61850 is the substation standard many utilities ask for.
Ethernet, RS485, CAN, Modbus TCP, Modbus RTU
Grid functions
Off-grid / black start Off-grid / black start: Whether the PCS can run your loads while the grid is down (off-grid) and restart a dead system from the battery alone (black start). Needed if you want backup during outages, not just bill savings.
Yes
Grid-forming Grid-forming: A grid-forming PCS sets its own voltage and frequency, like a generator, instead of following the grid's. It can help steady a weak grid and run a microgrid; a grid-following unit needs a stable grid to lock onto.
Not stated
Certification
Certifications Certifications: The safety and grid standards it is tested to. IEC 62477-1 covers converter safety, IEC 61000-6 electromagnetic compatibility (interference), and UL 1741 and IEEE 1547 are North American grid-connection standards. In India, grid connection must also meet CEA's connectivity rules; ask whether the unit holds any BIS (IS) certification your project needs.
NA
Size:
215 kW
Model code:
ESHV215K-LI-G01
Checked:
November 2026, against the datasheet
Note
For liquid-cooled battery cabinets; max coolant temperature 58 °C.
HPPS-1000010 MW central PCS turnkey station with MV transformer
HPPS-25002.5 MW central PCS turnkey station with MV transformer
HPPS-50005 MW central PCS turnkey station with MV transformer
Hopewind ESHV215K-LI-G01, in short
The Hopewind ESHV215K-LI-G01 is a PCS rated 215 kW, with cooling Liquid and MV transformer built in: no. 3 other PCS at 215 kW are listed, from 2 makers. Hopewind has 6 other PCS on this site.
What are the main specifications of the Hopewind ESHV215K-LI-G01?
Rated 215 kW; Cooling Liquid; MV transformer built in: no. As printed on Hopewind's datasheet (checked November 2026); the full list is on this page.
Where can I find the Hopewind ESHV215K-LI-G01 datasheet?
Hopewind publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
What are the alternatives to the Hopewind ESHV215K-LI-G01?
Other 215 kW PCS sold in India include Huawei Digital Power LUNA2000-213KTL-H0, Hopewind ESHV Series 145~250kW and Hopewind ESHV Series 186~290kW 800Vac.
Who makes the Hopewind ESHV215K-LI-G01?
Hopewind, with its head office in Shenzhen, China. It has 7 PCS on this site, including this one.
Spot a wrong or outdated figure?Report a correction and we'll check it against the maker's current sheet.
Values as Hopewind prints them in the linked datasheet; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with Hopewind. Product and company names are trademarks of their owners, used only to identify the product.