Sungrow SC4000UD-MV

Listed A–Z, not ranked · Reviewed November 2026

MV power conversion unit with medium-voltage transformer · PCS by Sungrow

As printed in the datasheet, checked November 2026 (the date we compared these figures with the maker's sheet). NA means not published.

AC side

Rated power
4000 kW
Printed ratings
4000 kW
Nominal AC voltage
800 V
Grid frequency
50/60

DC side

DC voltage range
1150–1500 V
Max DC current
NA

Performance

Max efficiency
NA

Build

Type
NA
Cooling
Air
Ingress protection
IP54 (Converter: IP65)
Operating temperature
-35–60 °C
Weight
17000 kg
MV transformer built in
Yes
Communication
RS485, CAN, Ethernet

Grid functions

Off-grid / black start
Yes
Grid-forming
Not stated

Certification

Certifications
CE, IEC 62477-1, IEC 61000-6-2, IEC 61000-6-4
Size:
4000 kW
Model code:
SC4000UD-MV
Checked:
November 2026, against the datasheet

Note

MV power station (PCS with MV transformer); figures are for the station.

Full datasheet

Every row the maker prints, copied as written, read 2026-11-15.

Overview

Product
MV Power Conversion Unit
Models
SC4000UD-MV

DC side

DC voltage range
1150 – 1500 V
Min. DC voltage
1150 V
Max. DC voltage
1500 V1500 V(sungrowpower.com)
Max. DC current
1952 A * 2
Number of DC inputs
2

AC side

Rated AC power
4000 kVA @ 45 ℃ / 4400 kVA @ 30 ℃
Nominal AC voltage
800 V
AC voltage range
704 – 880 V
Grid frequency range
50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
Max. AC current
2886 A @ 45 ℃ / 3174 A @ 30 ℃
Power factor
>0.99 / 1 leading – 1 lagging
Reactive power
-100 % – 100 %
Current harmonic distortion (THDi)
< 3 % (at nominal power)
Feed-in phases / AC connection
3/3

Off-grid operation

Off-grid output voltage
800 V
Off-grid AC voltage range
704 – 880 V
Off-grid frequency
50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
Off-grid voltage distortion (THDu)
< 3 % (Linear load)
DC voltage component
< 0.5 % Un (Linear balance load)
Unbalanced load capacity
100 %

Efficiency

Max. efficiency
99 %99 %(sungrowpower.com)

Grid support

Grid support
L/HVRT, FRT, active & reactive power control and power ramp rate control, Volt-var, Volt-watt, Frequency-watt

Protection

DC protection and disconnection
DC load switch + fuse
AC protection and disconnection
AC circuit breakerMV load switch + fuse
Overvoltage protection
DC Type II / AC Type II
Ground fault / insulation monitoring
Yes / YesYes
Overvoltage and overtemperature
Yes

MV transformer and switchgear

MV / LV voltage
0.8 kV / 20 – 35 kV
Transformer rated power
4000 kVA
Transformer max. power
4400 kVA
Transformer vector group
Dy11
Transformer cooling
ONAN
Transformer oil
Mineral oil (PCB free) or degradable oil on request

Environment

Operating temperature
-35 to 60 ℃ (> 45℃ derating)-35~60 ℃(sungrowpower.com)
Relative humidity
0 – 100 %
Max. altitude
4000 m (> 2000m derating)
Ingress protection
IP54 (Converter: IP65)IP54(sungrowpower.com)
Cooling
Temperature controlled forced air cooling

Physical

Dimensions (W × H × D)
6058*2896*2438 mm
Weight
17000 kg

Communication

Communication
RS485, CAN, Ethernet
Display / user interface
LED, WEB HMI

Certifications

Certifications and standards
CE, IEC 62477-1, IEC 61000-6-2, IEC 61000-6-4

Features

Features
Advanced three-level technology, max. efficiency 99%Effective forced air cooling, no derating up to 45°CWide DC voltage operation window, full power operation at 1500 VModular design, easy for maintenanceIP65 protection degree, easy for outdoor installationC5 anti-corrosion degree, adjust to applications close to the seaBidirectional power conversion system with full four-quadrant operationCompatible with high voltage battery system, low system costBattery charge & dis-charge management and black start function integratedCompliant with CE, IEC 62477, IEC 61000 and grid regulationsFast active/reactive power responseL/HVRT, FRT, soft start/stop, specified power factor control and reactive power supportL/HVRT, L/HFRT, soft start/stop, specifiec power factor control and reactive power support(sungrowpower.com)

More PCS from Sungrow

Sungrow SC4000UD-MV, in short

The Sungrow SC4000UD-MV is a PCS rated 4000 kW, with cooling Air and MV transformer built in. 2 other PCS at 4000 kW are listed, from 1 maker. Sungrow has 3 other PCS on this site.

Same size from other makers: Kehua BCS4000K~5000K-C-HUD-NP/T4, Kehua BCS4000K~5000K-C-HUD/T4 Series

Questions about the Sungrow SC4000UD-MV

What are the main specifications of the Sungrow SC4000UD-MV?
Rated 4000 kW; Cooling Air; MV transformer built in. As printed on Sungrow's datasheet (checked November 2026); the full list is on this page.
Where can I find the Sungrow SC4000UD-MV datasheet?
Sungrow publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
What are the alternatives to the Sungrow SC4000UD-MV?
Other 4000 kW PCS sold in India include Kehua BCS4000K~5000K-C-HUD-NP/T4 and Kehua BCS4000K~5000K-C-HUD/T4 Series.
Who makes the Sungrow SC4000UD-MV?
Sungrow. It has 4 PCS on this site, including this one.

Spot a wrong or outdated figure? Report a correction and we'll check it against the maker's current sheet.

Values as Sungrow prints them in the linked datasheet; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with Sungrow. Product and company names are trademarks of their owners, used only to identify the product.

Not sure what to buy? Ask us what's compatible and what size fits your site.