Ingeteam INGECON SUN STORAGE 350TL

Listed A–Z, not ranked · Reviewed November 2026

Three-phase bidirectional string PCS for utility-scale storage (3Play TL Series) · PCS by Ingeteam

As printed in the datasheet, checked November 2026 (the date we compared these figures with the maker's sheet). NA means not published.

AC side

Rated power
260–346 kW
Printed ratings
260, 266, 273, 279, 286, 292, 299, 307, 316, 325, 346 kW
Nominal AC voltage
600–800 V
Grid frequency
50/60

DC side

DC voltage range
933–1500 V
Max DC current
280 A

Performance

Max efficiency
99.05 %

Build

Type
String
Cooling
Air
Ingress protection
IP66 / NEMA 4
Operating temperature
-30–60 °C
Weight
115 kg
MV transformer built in
No
Communication
Wi-Fi

Grid functions

Off-grid / black start
Yes
Grid-forming
Not stated

Certification

Certifications
EN 61000-6-1, EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN 61000-3-12, EN 62109-1, EN 62109-2, EN 50178, IEC 62116, IEC 61683, EN 50530, IEC 61727, EN 50549-1, EN 50549-2, CEI 0-21, CEI 0-16
Size:
8 sizes
Model code:
350TL (675 V / 690 V / 710 V / 730 V / 750 V / 800 V versions)
Checked:
November 2026, against the datasheet

Full datasheet

Every row the maker prints, copied as written, read 2026-11-15.

Overview

Description
Storage inverter for utility scale plants; Three-phase bidirectional Power Conversion System (PCS)Large-scale(ingeteam.com)
Power range
String inverter up to 350 kW; Utility Scale Battery String Inverter; Paralellizable; Advanced communications system; Easy to maintain; Maximum flexibility and scalability for any battery configuration; SPE (Single Pair Ethernet)(ingeteam.com)

DC side

DC voltage range
600 V: 933 - 1,500 V; 615 V: 957 - 1,500 V; 630 V: 980 - 1,500 V; 645 V: 1,003 - 1,500 V; 660 V: 1,027 - 1,500 V; 675 V: 1,050 - 1,500 V; 690 V: 1,073 - 1,500 V; 710 V: 1,104 - 1,500 V; 730 V: 1,136 - 1,500 V; 750 V: 1,167 - 1,500 V; 800 V: 1,245 - 1,500 V
Max. DC voltage
1,500 V
Max. DC current
280 A
Max. DC current (charge / discharge)
250 A
DC connection
Yes (please contact Ingeteam´s BESS Sales Department)

AC side

Rated AC power
600 V: 260 kVA; 615 V: 266 kVA; 630 V: 273 kVA; 645 V: 279 kVA; 660 V: 286 kVA; 675 V: 292 kVA; 690 V: 299 kVA; 710 V: 307 kVA; 730 V: 316 kVA; 750 V: 325 kVA; 800 V: 346 kVA
AC output power at 40 °C
346 kVA(ingeteam.com)
Ambient temperature for rated power
40ºC
Nominal AC voltage
600 V: 3 / PE, 600 V; 615 V: 3 / PE, 615 V; 630 V: 3 / PE, 630 V; 645 V: 3 / PE, 645 V; 660 V: 3 / PE, 660 V; 675 V: 3 / PE, 675 V; 690 V: 3 / PE, 690 V; 710 V: 3 / PE, 710 V; 730 V: 3 / PE, 730 V; 750 V: 3 / PE, 750 V; 800 V: 3 / PE, 800 V
AC voltage range
600 - 800 V
Grid frequency
50 / 60 Hz
Charge / discharge current at 40 °C
250 A(ingeteam.com)
Power factor
10 - 1(ingeteam.com)
Adjustable power factor
Yes, 0-1 (leading / lagging)
Current harmonic distortion (THDi)
<3%
Grid type
IT
AC connection
AC connection: max. cross section: 120 mm2 (one wire) copper / DC connection: up to 2 x 400 mm2 or 4 x 240 mm2 aluminium

Efficiency

Max. efficiency
99.05%
European efficiency
98.60%

Grid support

Grid support
Frequency regulation; Synthetic inertia; Frequency control / protection; Virtual "Synchronous Machine"
Grid functions
Ramp limits; Power smoothing / firming / curtailment; Time shifting; Micro grids; Black startPeak shaving; Load shifting / Load following; Real power response improvement of conventional power plantsTime shifting; Price arbitrage; Real power response improvement of conventional power plants; Peak shavingGrid code compliance; Transmission congestion relief / Power quality-reliabilityVoltage control (Q/V); Voltage control / protection; Fixed power factor (QPF); Fixed reactive power output (Qref); Limitation of response of Reactive Power

Protection

Residual current monitoring
Yes
Other protections
DC switch; Shortcircuits and overloads at the output; Anti-islanding with automatic disconnection; Insulation faults; AC overvoltages with type II surge arresters; DC overvoltages with type II surge arresters

Environment

Operating temperature
-30º C to 60º C-30º C to 60º C(ingeteam.com)
Relative humidity
0 - 100%
Max. altitude
4,000 m.a.s.l. (for installations beyond 1,000 m.a.s.l., please contact Ingeteam’s Solar Sales Department)
Ingress protection
IP66 / NEMA 4IP66 / NEMA 4(ingeteam.com)
Cooling
Forced ventilationForced air 900 m3/h(ingeteam.com)
Air flow
900 m3/h

Physical

Dimensions (mm)
1,045 / 1,045 / 400
Weight
350TL: 115 kg.
Installation
Aluminium casing, especially conceived for indoor and outdoor applications (IP66)

Auxiliary power

Own consumption in operation
20 W

Certifications

Certifications and standards
CEIEC Certification; UL Certification(ingeteam.com)
EMC standards
EN 61000-6-1, EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN 61000-3-12, EN 62109-1, EN 62109-2, EN 50178, IEC 62116, IEC 61683, EN 50530, IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-14, IEC 60068-2-30, IEC 60068-2-68
Grid codes
IEC 61727, EN 50549-1, EN 50549-2, UNE 206007-1 IN, NTS 2.1 SEPE, NTS 1.1 SENP, CEI 0-21, CEI 0-16, Arrete 9 du Juin, ABNT NBR 16149, ABNT NBR 16150, NDU-015, Portaria 73IEC 61727, EN 50549-1, EN 50549-2, UNE 206007-1 IN, NTS 2.1 SEPE, NTS 1.1 SENP, CEI 0-21, CEI 0-16, Arrete 9 du Juin, ABNT NBR 16149, ABNT NBR 16150, NDU-015, Portaria 73(ingeteam.com)

Features

Features
Maximum DC voltage (1,500 V) and wide voltage range. Awesome power density, with up to 350 kWCan be parallelized, on the AC side, to adjust the PCS power to different battery configurations; allows augmentation so old and new batteries can be mixed; the string inverter philosophy permits an easy and immediate replacement that does not require qualified techniciansSPE communication as standard; high-speed IP communication up to 1,000 meters; daisy chain connectionSupplied totally equipped with all the electrical protectionsAC quick connectors; DC switch; DC surge arresters, type II; AC surge arresters, type II; DC & AC pre-charge system; Wi-Fi communication; SPE (Single Pair Ethernet) communicationGreater power density; Flexibility and scability; High availability compared to central inverters; High efficiency rates; Easy maintenance
Diagrams
2x AC Relay; AC Filter; DC Filter; PE (IT System)

More PCS from Ingeteam

Ingeteam INGECON SUN STORAGE 350TL, in short

The Ingeteam INGECON SUN STORAGE 350TL is a PCS rated 260 kW, with max efficiency 99.05%, cooling Air and MV transformer built in: no. Its max efficiency (99.05%) is above the median of the 45 PCS listed (98.7%). Ingeteam has 6 other PCS on this site.

Questions about the Ingeteam INGECON SUN STORAGE 350TL

What are the main specifications of the Ingeteam INGECON SUN STORAGE 350TL?
Rated 260 kW; Max efficiency 99.05%; Cooling Air; MV transformer built in: no. As printed on Ingeteam's datasheet (checked November 2026); the full list is on this page.
Where can I find the Ingeteam INGECON SUN STORAGE 350TL datasheet?
Ingeteam publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
Who makes the Ingeteam INGECON SUN STORAGE 350TL?
Ingeteam. It has 7 PCS on this site, including this one.

Spot a wrong or outdated figure? Report a correction and we'll check it against the maker's current sheet.

Values as Ingeteam prints them in the linked datasheet; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with Ingeteam. Product and company names are trademarks of their owners, used only to identify the product.

Not sure what to buy? Ask us what's compatible and what size fits your site.