Listed A–Z, not ranked · Reviewed November 2026
Modular AC-DC battery inverter for 1500 V BESS (IEC version) · PCS by Ingeteam
Specifications
Datasheet on ingeteam.com(opens in a new tab)Product pageon ingeteam.com (opens in a new tab)
As printed in the datasheet, checked November 2026 (the date we compared these figures with the maker's sheet). NA means not published.
AC side
- Rated power
- 2961–4540 kW
- Printed ratings
- 2961, 3111, 3258, 3405, 3948, 4148, 4344, 4540 kW
- Nominal AC voltage
- 600–690 V
- Grid frequency
- 50/60
DC side
- DC voltage range
- 938–1500 V
- Max DC current
- NA
Performance
- Max efficiency
- 98.9 %
Build
- Type
- Modular
- Cooling
- Liquid
- Ingress protection
- IP65
- Operating temperature
- -20–60 °C
- Weight
- NA
- MV transformer built in
- No
- Communication
- NA
Grid functions
- Off-grid / black start
- Yes
- Grid-forming
- Not stated
Certification
- Certifications
- IEC 61477-1, IEC 60529, CISPR11, EN 55011, IEC 61000-6-2, IEC 61000-3-11, IEC 61000-3-12, IEC 62116, IEC 61683, IEC 61727, EN 50549-2, VDE-AR-N 4110/4120/4130, UK: G99
- Model code:
- INGECON SUN STORAGE 4540TL (M600 / M630 / M660 / M690, each with 3 or 4 modules: M3 / M4)
- Checked:
- November 2026, against the datasheet
Full datasheet
Every row the maker prints, copied as written, read 2026-11-15.
Overview
- Description
- Up to 4.54 MVA with four modules of 1.14 MVA; AC-DC modular converter for 1500 V battery energy storage systemsThree-phase bidirectional battery inverter that can be used in grid-connected and stand-alone systems; matching any type of batteries at different range of hour of applicationLarge-scale; Batteries(ingeteam.com)
- Power range
- Modular central inverter up to 4.55 MW; Modular Battery Inverter for Utility Scale BESS Projects; Up to 4.5 MW; Configuration of 3 or 4 modules of 1.14 MVA per inverter; Grid Forming functionality by default; Power density of 488 kVA/m³; Integrated control unit; Intended for both Grid-Tied and Grid-Forming AC-coupled utility-scale storage systems(ingeteam.com)
DC side
- Battery voltage, grid-tied mode (V)
- M600: 938 to 1,500; M630: 984 to 1,500; M660: 1,035 to 1,500; M690: 1,077 to 1,500
- Battery voltage, off-grid mode (V)
- M600: 854 to 1,500; M630: 896 to 1,500; M660: 938 to 1,500; M690: 980 to 1,500
- DC short-circuit withstand per input (kA)
- 250 (< 5ms)
- Number of DC inputs
- M3: 1/3; M4: 1/2/4
- DC inputs per inverter
- M3: 15; M4: 20
- DC inputs per module
- 5
- Inputs with fuse-holders
- Up to 630 A / 1,500 V / aR (optional)
- DC connection
- Connection to copper bars
AC side
- AC output power at 40 °C
- 4,540 kVA(ingeteam.com)
- AC output power at 40 °C (kVA/kW)
- M600 M3: 2,961; M600 M4: 3,948; M630 M3: 3,111; M630 M4: 4,148; M660 M3: 3,258; M660 M4: 4,344; M690 M3: 3,405; M690 M4: 4,540
- Nominal AC voltage (V)
- M600: 600; M630: 630; M660: 660; M690: 690
- Grid frequency (Hz)
- 50 / 60
- Max. AC output current at 40 °C (A)
- M3: 2,850; M4: 3,800
- Charge / discharge current at 40 °C
- 3,800 kVA(ingeteam.com)
- Power factor
- 0 - 1(ingeteam.com)
- Adjustable power factor
- 0 - 1 (leading / lagging)
- Current harmonic distortion (THDi)
- <3%
Efficiency
- Max. efficiency
- 98.9%
- CEC efficiency
- 98.5%
Grid support
- Grid support
- Frequency regulation; Synthetic inertia; Black start; Frequency control / protection; Virtual "Synchronous Machine"
- Grid functions
- Ramp limits; Power smoothing / firming / curtailment; Time shifting; Micro gridsPeak shaving; Load shifting / Load following; Real power response improvement of conventional power plantsTime shifting; Price arbitrage; Real power response improvement of conventional power plants; Peak shaving"Un-interruptible" Power; Grid code compliance; Transmission congestion relief / Power quality-reliabilityVoltage control (Q/V); Voltage control / protection; Fixed power factor (QPF); Fixed reactive power output (Qref); Limitation of response of Reactive Power
Protection
- DC protection and disconnection
- Motorized DC load break disconnect
- AC protection and disconnection
- Motorized AC circuit breaker
- Overvoltage protection
- Type I+II surge arrestersType II surge arresters (type I+II optional)
- Anti-islanding
- Yes, with automatic disconnection
- Other protections
- Short-circuits and overloads at the output; Anti-islanding with automatic disconnection; Insulation failure DC; Monitoring of the DC currents; Up to 5 pairs of fuse-holders; Lightning induced DC and AC surge arresters, type II; Motorized DC switch; Motorized AC circuit breaker; Hardware protection via firmware; Additional protection for the power stack, liquid cooled, IP65 rated and air cooled by a closed loopUp to 5 pairs of DC fuses per power module (optional) / Reverse polarity / Insulation failure monitoring / Anti-islanding protectionAC short-circuits and overloads
Environment
- Operating temperature
- -20 °C to +60 °C(ingeteam.com)
- Operating temperature (°C)
- -20 to +60
- Operating temperature with heating kit (°C)
- -40 to +60
- Relative humidity
- 0-100% (Outdoor)
- Max. altitude (m above sea level)
- 4,500 (for installations beyond 1,000 m, please contact Ingeteam’s solar sales department)
- Ingress protection
- IP65IP65(ingeteam.com)
- Anti-corrosion
- C5M External corrosion protection
- Cooling
- Liquid cooling system and forced air cooling system with temperature control (400V 3 phase + neutral power supply, 50/60 Hz)Liquid cooling system and forced air cooling system with temperature control(ingeteam.com)
- Air flow (m³/h)
- 0–27,00018,000
Physical
- Dimensions L × W × H (mm)
- 5,200 x 900 x 2,200
Auxiliary power
- Standby consumption (W)
- 925
Certifications
- Certifications and standards
- CEIEC Certification; UL Certification(ingeteam.com)
- EMC standards
- IEC 61477-1, IEC 60529, CISPR11, EN 55011, IEC 61000-6-2, IEC 61000-3-11, IEC 61000-3-12; IEC 62116, IEC 61683
- Grid codes
- IEC 61727, EN 50549-2, ES: NTS SEPE&SENP, ES: UNE 217002, DE: VDE-AR-N 4110/4120/4130, IT: CEI 016 (allegato N), IT: Allegato A79, UK: G99, FR: Arrete 9 du Juin, BE: C10/C11, RO: Ord 208, MEX: CRE, BR: SUBMODULO 2.10IEC 61727, EN 50549-2, ES: NTS SEPE&SENP, ES: UNE 217002, DE: VDE-AR-N 4110/4120/4130, IT: CEI 016 (allegato N), IT: Allegato A68, UK: G99, FR: Arrete 9 du Juin, BE: C10/C11, RO: Ord 208, MEX: CRE, BR: SUBMODULO 2.10(ingeteam.com)
- Warranty
- Standard 5 years, extendible upon request
Features
- Features
- Market-leading power density of 488 kW/m3; up to 1.14 MVA in just one power moduleInnovative control unit using a last-generation digital signal processorRefrigerates the IGBTs, the power phases and the IP65 / NEMA 3 compartment; closed circuit supplied totally filled and purged; biodegradable glycol water mixtureA secondary liquid cooling system refrigerates the air inside the IP65 / NEMA 3 protected compartment via a water-air heat exchangerNominal power at 40 °C ambient; Same charge / discharge power; Modularity, adapts to customer demandLCS to refrigerate the IGBTs; More optimized component usage: greater thermal stability; Less moving components: lower power consumption and less maintenance works; No risk of particle entrance; Anti-corrosion protection with stainless steel components; LCS is used in many industries. Thus, it is very reliable, as its components are subject to many validation tests; Fast connectors with anti-dripping system; Biodegradable glycol water mixture; No need of emptying the LCS in order to replace the phases, nor the sensorsSolution for independent Racks: modular inverter working independently to its battery racks; Solution for battery containers with a single output: modular inverter working in parallel; SLD with 2 inverters per power station
- Options and accessories
- Heating kit, for operating at an ambient temperature between -20 °C and -40 °C; DC fuses in the positive pole or in both poles; DC surge arresters type I+II; AC surge arresters type I+II; AC measuring kit
More PCS from Ingeteam
- INGECON SUN STORAGE 100TLThree-phase battery inverter for C&I storage (3Play TL Series)
- INGECON SUN STORAGE 350TLThree-phase bidirectional string PCS for utility-scale storage (3Play TL Series)
- INGECON SUN STORAGE 3Power C Series HVThree-phase transformerless 1500 V battery inverter (IEC version)
- INGECON SUN STORAGE FSK C Series HVFull-skid MV power station with C Series HV storage inverters (no batteries)
- PowerStation FSK M SeriesINGECON SUN STORAGE. MV skid power station with M Series storage inverters, step-up transformer and RMU (no batteries)
- PowerStation PMT M SeriesINGECON SUN STORAGE. MV power station with M Series inverters and pad-mounted transformer, UL 1741 SB (no batteries)
Ingeteam INGECON SUN STORAGE 3Power M Series, in short
The Ingeteam INGECON SUN STORAGE 3Power M Series is a PCS rated 3000 kW, with max efficiency 98.9%, cooling Liquid and MV transformer built in: no. Its max efficiency (98.9%) is above the median of the 45 PCS listed (98.7%). 4 other PCS at 3000 kW are listed, from 4 makers. Ingeteam has 6 other PCS on this site.
Same size from other makers: FIMER PVS980-58BC-3750-L, Hitachi Energy India PCS WD3, Kehua BCS2500K~3450K-B-HUD/T Series, Ingeteam INGECON SUN STORAGE 3Power C Series HV · All 3000 kW side by side
Questions about the Ingeteam INGECON SUN STORAGE 3Power M Series
- What are the main specifications of the Ingeteam INGECON SUN STORAGE 3Power M Series?
- Rated 3000 kW; Max efficiency 98.9%; Cooling Liquid; MV transformer built in: no. As printed on Ingeteam's datasheet (checked November 2026); the full list is on this page.
- Where can I find the Ingeteam INGECON SUN STORAGE 3Power M Series datasheet?
- Ingeteam publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
- What are the alternatives to the Ingeteam INGECON SUN STORAGE 3Power M Series?
- Other 3000 kW PCS sold in India include FIMER PVS980-58BC-3750-L, Hitachi Energy India PCS WD3, Kehua BCS2500K~3450K-B-HUD/T Series and Ingeteam INGECON SUN STORAGE 3Power C Series HV. All of them are compared side by side on the 3000 kW page.
- Who makes the Ingeteam INGECON SUN STORAGE 3Power M Series?
- Ingeteam. It has 7 PCS on this site, including this one.
Spot a wrong or outdated figure? Report a correction and we'll check it against the maker's current sheet.
Values as Ingeteam prints them in the linked datasheet; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with Ingeteam. Product and company names are trademarks of their owners, used only to identify the product.