Rating

Rated energy
NA
Rated power
50–60 kW
Charge/discharge rate
NA
Duration
NA
PCS included
Yes
Cooling
NA

Battery

Cell capacity
100 Ah
Chemistry
LFP
DC voltage range
350–820 V
Cycle life
6000 cycles

Electrical

AC voltage
400 V
AC frequency
NA
Round-trip efficiency
NA
Efficiency measured
NA

Physical

Size (mm)
NA
Weight
NA
Enclosure rating
NA

Environment

Operating temperature
-30–60 °C
Max altitude
NA
Noise at 1 m
NA

Safety

Fire suppression
NA
Certifications
NA
Model code:
MTX-H60
Checked:
November 2026, against the spec page

Full datasheet

Every row the maker prints, copied as written, read 2026-11-15.

Overview

Model
MTX-H60MTX Hybrid 50 / 60
Product line
Commercial & Industrial · 30 kW – 2 MW
Description
Solar + storage + backup in one cabinet. The MTX Hybrid integrates two MPPTs (38.4 kW each) and a built-in switching device for grid ↔ off-grid transfer in under 10 ms, with 100% unbalanced-load support on a 400/230 V four-wire output.

Battery

Cell type
LiFePO4 · 3.2 V 100 Ah · ~6,000 cycles*
Cell
Grade-A 3.2 V LFP — 100 Ah cells for 30–250 kW systems, 314 Ah cells for 250 kW–2 MW PTX and CTX containers. Capacity- and IR-matched per pack.(tobor.in)320 Wh · 1.0 kWh(tobor.in)
Rated energy
Sized to runtime(tobor.in)
DC voltage range
350–820 V (50 kVA) · 420–820 V (60 kVA)
Max current
150 A

Power and grid

Rated AC power
60 kW50 / 60 kVA50 / 60 kW at unity PF
PCS
Bidirectional power modules — 30 kW in MTX cabinets (with solar MPPT on MTX Hybrid), 125 kW PMs at 98.5% peak efficiency in PTX and CTX. Grid-tied, off-grid and island modes.(tobor.in)
Max apparent output
50 / 60 kVA · peak 55 / 66 kVA
Rated AC current
73 A / 87 A
AC voltage
400 / 230 V · 3-phase 4-wire
AC voltage range
-20% → +20%
PCS efficiency
97.8%
PCS cooling
Forced air · IP20 PM inside cabinet
Unbalanced load capacity
100%
Units in parallel
Up to 15 PMs
On/off-grid switching
< 10 ms< 10 ms (PM specification)The MTX Hybrid switches grid ↔ off-grid in under 10 milliseconds — compatibility with sensitive or medical loads must be verified for the specific installation.(tobor.in)

Solar and generator

Solar (MPPT) power
2 × 38.4 kW MPPT
Solar (MPPT) voltage range
200–800 V
Solar (MPPT) max voltage
250 V / 850 V
MPPT inputs
2 MPPTs · 38.4 + 38.4 kW
Max PV inverter input current
64 A + 64 A
Works with
Grid · Solar PV · DG · EV charging

Environment

Operating temperature
-30 °C → +60 °C (derates above 45 °C)

Physical

Form factor
Solar-hybrid cabinet · 50 / 60 kVA
Installation
MTX cabinets (about 1.65 × 1.0 m) are floor-standing — typically inside a utility room next to the existing DG room.(tobor.in)
Installation time
MTX cabinets (30–60 kW) and PTX systems up to 250 kW take 2–4 days on site, depending on civil work and existing wiring.(tobor.in)

Communication

Communication
EMS RS485 · battery CAN / RS485
Remote monitoring
Cloud EMS dashboard · remote diagnostics
BMS / EMS
In-house TOBOR BMSIn-house TOBOR EMS

Features

Application
Commercial rooftop solar · critical loads · 3-phase unbalanced sitesPeak shaving · ToU shifting · Solar self-use · Backup reserve

More BESS cabinets from Tobor

Tobor MTX Hybrid 50 / 60, in short

The Tobor MTX Hybrid 50 / 60 is a cabinet BESS, with rated power 50–60 kW and PCS included. Tobor has 2 other cabinet BESS on this site.

Questions about the Tobor MTX Hybrid 50 / 60

What are the main specifications of the Tobor MTX Hybrid 50 / 60?
Rated power 50–60 kW; PCS included. As printed on Tobor's spec page (checked November 2026); the full list is on this page.
Where can I find the Tobor MTX Hybrid 50 / 60 spec page?
Tobor publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
Who makes the Tobor MTX Hybrid 50 / 60?
Tobor, with its head office in Gurugram. It has 3 cabinet BESS on this site, including this one.

Spot a wrong or outdated figure? Report a correction and we'll check it against the maker's current sheet.

Values as Tobor prints them in the linked spec page; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with Tobor. Product and company names are trademarks of their owners, used only to identify the product.

Not sure what to buy? Ask us what's compatible and what size fits your site.