11 products from 8 companies, side by side. All 122 products in DG sets · Listed A–Z, not ranked · Reviewed November 2026
500 kVA is a standard size for large industrial and commercial sites and for data centres that run several sets in parallel. Check the rating basis, engine and control panel, and the space and foundation the set needs.
500 kVA compared
A–Z by company, not ranked · NA: not published by the maker
| Field | Cummins IndiaK19 Series500 kVA, 400 kWe Prime | Cummins IndiaQSM15 Series380 - 500 kVA, 304 - 400 kWe Prime | Force MTU Power SystemsSeries 1600Diesel generator sets, made by Force MTU | Genlite EngineeringSterling Green SGB PR-IVBaudouin-engined diesel gensets, 320 to 750 kVA | Jakson GroupJSP-IVSilent diesel generating sets, radiator cooled, 7.5 to 750 kVA | Kirloskar Oil EnginesKG4-500WS500 kVA Diesel Generator | Kirloskar Oil EnginesKG4-500WS NG1500 kVA Natural Gas Generator | Kirloskar Oil EnginesOptiprime 500 kVA500 kVA Optiprime | Mahindra PowerolM10DR to M650DRAcoustic DG sets, 10 to 650 kVA | Ojus Power and Technologies500 kVADiesel genset model | Sudhir PowerCS D5P seriesCummins-powered silent diesel gensets (2023 brochure) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Output | |||||||||||
| Rating | 500 kVA | 380–500 kVA | 500–910 kVA | 320–750 kVA | 7.5–750 kVA | 500 kVA | 500 kVA | 500 kVA | 10–650 kVA | 500 kVA | 7.5–2250 kVA |
| Power output | 400 kWe | from 304 kWe | NA | 256–600 kWe | 6–600 kWe | 400 kWe | NA | 400 kWe | 8–520 kWe | 400 kWe | NA |
| Printed ratings | 500 kVA | 380, 400, 500 kVA | NA | 320, 400, 450, 500, 650, 750 kVA | 7.5, 10, 15, 18.5, 20, 25, 27.5, 30, 35, 40, 41, 50, 58.5, 82.5, 100, 125, 140, 160, 180, 200, 225, 250, 320, 380, 400, 500, 650, 750 kVA | 500 kVA | 500 kVA | 500 kVA | 10, 15, 20, 25, 30, 35, 40, 45, 50, 58.5, 62.5, 82.5, 100, 125, 160, 180, 200, 250, 320, 400, 500, 525, 650 kVA | NA | 7.5, 10, 15, 20, 25, 30, 35, 40, 50, 62.5, 82.5, 100, 125, 140, 160, 180, 200, 225, 250, 275, 300, 320, 380, 400, 500, 600, 625, 650, 750, 810, 910, 1010, 1250, 1500, 1800, 2000, 2250 kVA |
| Rating basis | Prime | Prime | NA | NA | NA | Prime | NA | Prime | NA | Prime | Prime |
| Output voltage | 415 | 415 | NA | 415 | NA | 415 (3ɸ) | 230 V | 415 (3ɸ) | 230/415 (10 to 40 kVA), 415 (3 phase) above | 415 | NA |
| Frequency | 50 Hz | 50 Hz | NA | 50 Hz | NA | 50 Hz | 50 Hz | 50 Hz | 50 Hz | 50 Hz | NA |
| Power factor | 0.8 (lagging) | 0.8 (lagging) | NA | 0.8 | NA | 0.8 | NA | 0.8 | 0.8 lagging | 0.8 | NA |
| Phase | 3-phase | 3-phase | NA | NA | 1-phase, 3-phase | 3-phase | NA | 3-phase | 1-phase, 3-phase | 3-phase | NA |
| Build | |||||||||||
| Fuel | Diesel | Diesel | Diesel | Diesel | Diesel | Diesel | Gas | Diesel | NA | Diesel | NA |
| Engine | Cummins KTAA19-G10 | Cummins QSM15-G1 | MTU Series 1600 | Baudouin 6M21G0D4/5 to 6M33G4D4/5 | X2.5-G5 to QSK19-G30 (and others) | DV8ETA 4G3 | DV12TA NG1 | 6K1080ETA 4G2 | Mahindra M2155G1 and others; Perkins 2806FA-E18TAG1 and 2806FA-E18TAG2 for 400 to 650 kVA | Baudouin 6M21G6D4/5 | X1.3TAA-G1, X1.3TAA-G7 |
| Alternator | Stamford HCI544D | STAMFORD HCI444E, HCI444F and HCI544D | NA | Leroy Somer and Stamford make, brushless, self excited, IP 23, class H/H insulation, single bearing | NA | NA | NA | NA | CG/LS/Equivalent | Stamford HCI544V | NA |
| Enclosure | Acoustic | Acoustic | NA | NA | Acoustic | Acoustic | Acoustic | Acoustic | Acoustic | NA | Acoustic |
| Dimensions (L × W × H) | 6000 × 2000 × 2250 mm (axes not stated) | 5300 × 1900 × 2490 mm (axes not stated) | NA | 7200 × 2200 × 3395 mm (axes not stated) | 6800 × 2050 × 2860 mm (axes not stated) | 5575 × 2125 × 2610 mm (axes not stated) | 6518 × 2123 × 2708 mm (axes not stated) | 3050 × 2130 × 1442 mm (axes not stated) | 5800 × 2200 × 2300 mm (axes not stated) | 5700 × 2100 × 3113 mm (axes not stated) | 10450 × 3500 × 3800 mm (axes not stated) |
| Fuel tank capacity | 690 | 715 to 745 | NA | 900 to 990 | 85 to 980 | NA | NA | NA | 55 to 800 | 900 | NA |
| Weight | about 7600 kg | about 5515–5915 kg | NA | about 6480–8800 kg | about 772–10156 kg | 6435 kg | 7800 kg | 6160 kg | 690–3920 kg | 6871 kg | NA |
| Certification | |||||||||||
| CPCB IV+ | NA | Yes | NA | Yes | Yes | Yes | NA | Yes | NA | NA | NA |
| Certifications and standards | IS/IEC 60034-1, ISO 8528, ISO 3046, IS 1460, ISO 9001, IS 13018 | IS/IEC 60034-1, ISO 8528, ISO 3046, IS 1460, ISO 9001, IS 13018 | NA | ISO, AS/NZ, IEC, IEEE, BS | NA | ISO 8528 | ISO 8528 | ISO 8528 | IS/IEC60034-1 (alternator) | ISO 8528, ISO 3046-1, ISO 15550 | NA |
| Performance | |||||||||||
| Governing class | ISO 8528-5 G2 | ISO 8528-5 G2 | NA | G3 | G2/G3 | G3 | NA | NA | G2/G3 | G3 as per ISO 8528-5 | NA |
| Fuel consumption | 79.83 L/h at 75% load | NA | NA | 117 L/h at 75% load (largest set) | NA | NA | NA | NA | NA | 75.4 L/h at 75% load | NA |
| Noise level | 75 dBA at 1 m, 75% load, free field | 75 dBA at 1 m, 75% load, free field | NA | NA | NA | <75 dBA | < 75 dB(A) | <75 DBA | NA | NA | 75 dBA at 1 m |
| Controls | |||||||||||
| Controller | Cummins PowerCommand 1.2 | Cummins PowerStart PS0602 | NA | DEIF SGC 420 MK | NA | NA | NA | NA | GC 1115 (10 to 200 kVA), GC 1116 (250 and 320 kVA), DSE7320 (400 to 650 kVA) | DEIF SGC 420 MK II | PS0600/1/2 (15-1010 kVA); PCC 3201 (1250-3750 kVA) |
| Support | |||||||||||
| Warranty | 5 Yrs engine critical parts warranty | 5 Yrs engine critical parts warranty | NA | NA | 5C Warranty (5 years/ 5000 hours) | NA | NA | 5-year standard warranty | Standard warranty of 2 Years/5000 Hours, 5 Years 5C warranty | NA | NA |
| Source | |||||||||||
| Note | Power range as printed on the company product page. | Sheet lists six models from 320 to 750 kVA. Higher ratings are available on request. | Dimensions, weight and day fuel tank are for the acoustic set. | ||||||||
| Model code | C500D5P | CI 380D5P, CI 400D5P, CI 500D5P | FM500, FM610, FM1000 | SGB 320 PR-IV, SGB 400 PR-IV, SGB 450 PR-IV, SGB 500 PR-IV, SGB 650 PR-IV, SGB 750 PR-IV | JSP-IV 7.5 to JSP-IV 750 | NA | NA | NA | M10DR to M650DR | NA | CS 7.5 D5P to CS 2250 D5P |
| Datasheet | Datasheet (PDF) of Cummins India K19 Series (opens the maker's site) | Datasheet (PDF) of Cummins India QSM15 Series (opens the maker's site) | Spec page of Force MTU Power Systems Series 1600 (opens the maker's site) | Datasheet (PDF) of Genlite Engineering Sterling Green SGB PR-IV (opens the maker's site) | Datasheet (PDF) of Jakson Group JSP-IV (opens the maker's site) | Spec page of Kirloskar Oil Engines KG4-500WS (opens the maker's site) | Spec page of Kirloskar Oil Engines KG4-500WS NG1 (opens the maker's site) | Spec page of Kirloskar Oil Engines Optiprime 500 kVA (opens the maker's site) | Datasheet (PDF) of Mahindra Powerol M10DR to M650DR (opens the maker's site) | Datasheet (PDF) of Ojus Power and Technologies 500 kVA (opens the maker's site) | Datasheet (PDF) of Sudhir Power CS D5P series (opens the maker's site) |
| CheckedFigures compared with the maker's sheet | November 2026 | November 2026 | November 2026 | November 2026 | November 2026 | November 2026 | November 2026 | November 2026 | November 2026 | November 2026 | November 2026 |
| Details | Details of Cummins India K19 Series | Details of Cummins India QSM15 Series | Details of Force MTU Power Systems Series 1600 | Details of Genlite Engineering Sterling Green SGB PR-IV | Details of Jakson Group JSP-IV | Details of Kirloskar Oil Engines KG4-500WS | Details of Kirloskar Oil Engines KG4-500WS NG1 | Details of Kirloskar Oil Engines Optiprime 500 kVA | Details of Mahindra Powerol M10DR to M650DR | Details of Ojus Power and Technologies 500 kVA | Details of Sudhir Power CS D5P series |
Values as each maker prints them on its own datasheet or spec page, linked in the Datasheet row at the foot of the table; Checked is the date we compared these figures with the maker's sheet. Each rating is shown with the basis its maker prints (prime, standby or not stated); prime and standby figures are not the same and shouldn't be compared directly. A range covers the variants on one sheet. Nothing here is tested by Ingro Energy, and the order is alphabetical by company.
What differs between them
Counted from the 11 products above, as printed.
- Rating: 7.5 to 2250 kVA as printed (ranges included)
- Power output: 6 to 600 kWe as printed (ranges included); 3 not published
- Rating basis: Prime; 6 of 11 publish it
- Fuel: 8 Diesel, 1 Gas; 2 not published
- CPCB IV+: 5 of 11; 6 not published
- Output voltage: 8 of 11 publish it; values in the table
- Frequency: 50 Hz; 8 of 11 publish it
- Power factor: 0.8 on 4, 0.8 (lagging) on 2, 0.8 lagging on 1; 4 not published
- Governing class: 7 of 11 publish it; values in the table
- Phase: 7 of 11 publish a list; 3-phase on 7, 1-phase on 2
- Engine: 11 of 11 publish it; values in the table
- Alternator: 5 of 11 publish it; values in the table
- Enclosure: Acoustic; 8 of 11 publish it
- Fuel consumption: 3 of 11 publish it; values in the table
- Noise level: 6 of 11 publish it; values in the table
- Controller: 6 of 11 publish it; values in the table
- Dimensions (L × W × H): 10 of 11 publish it; values in the table
- Fuel tank capacity: 55 to 800 on 1, 690 on 1, 715 to 745 on 1, 85 to 980 on 1, 900 on 1, 900 to 990 on 1; 5 not published
- Weight: 690 to 10156 kg as printed (ranges included); 2 not published (4 printed as approximate)
- Warranty: 5 of 11 publish it; values in the table
- Certifications and standards: 8 of 11 publish a list; ISO 8528 on 6, IS 13018 on 2, IS 1460 on 2, IS/IEC 60034-1 on 2
Nearby rating values
A page needs 3+ products from 3+ companies; values without one are in the full list by rating.
- 400 kVA8 products
- 450 kVA2 products
- 525 kVA1 product
- 600 kVA2 products
Questions about 500 kVA DG sets (diesel and gas generator sets)
- Which companies make 500 kVA DG sets (diesel and gas generator sets) in India?
- 8 companies list 11 products at this size: Cummins India (K19 Series, QSM15 Series); Force MTU Power Systems (Series 1600); Genlite Engineering (Sterling Green SGB PR-IV); Jakson Group (JSP-IV); Kirloskar Oil Engines (KG4-500WS, KG4-500WS NG1, Optiprime 500 kVA); Mahindra Powerol (M10DR to M650DR); Ojus Power and Technologies (500 kVA); Sudhir Power (CS D5P series). They are listed A–Z by company, not ranked.
- How do these 500 kVA DG sets (diesel and gas generator sets) differ?
- Rating: 7.5 to 2250 kVA as printed (ranges included). Power output: 6 to 600 kWe as printed (ranges included); 3 not published. Rating basis: Prime; 6 of 11 publish it. Fuel: 8 Diesel, 1 Gas; 2 not published. Counted from the 11 products as each maker prints them.
- Where do these figures come from?
- From each maker's own datasheet or spec page, checked November 2026. Products printed within ±3% of 500 kVA are grouped on this page, each showing its own printed figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with the companies listed.
Is your company on this list? Add it, update your details or raise a concern →