5 products from 3 companies, side by side. All 68 products in PCS · Listed A–Z, not ranked · Reviewed November 2026
A 2000 kW (2 MW) PCS is a utility-scale converter size, used to connect one or two battery containers to the grid for solar-plus-storage, peak supply and grid services. Some products listed here are MV power stations, with the PCS and a medium-voltage step-up transformer in one unit, and others are the converter alone; their efficiency and weight figures cover different things, so compare like with like.
2000 kW compared
A–Z by company, not ranked · NA: not published by the maker
| Field | FIMERPVS980-58BC-2091kVA-LBidirectional converter, 1454–2091 kVA (IEC/UL version, 1.6–2.3 MVA sheet) | FIMERPVS980-58BC-2500-LBidirectional converter, 1738–2500 kVA (IEC version, 2500-L sheet) | KehuaBCS2000K~2500K-C-HUD-NP/T2 Series | KehuaBCS2000K~2500K-C-HUD/T2 Series | SungrowSC2000UDPower conversion system |
|---|---|---|---|---|---|
| AC side | |||||
| Rated power | 1454–2091 kW | 1738–2500 kW | 2000–2500 kW | 2000–2500 kW | 2000 kW |
| Printed ratings | 1454, 1575, 1696, 1818, 1909, 2000, 2091 kW | 1738, 1883, 2028, 2173, 2282, 2390, 2500 kW | 2000, 2500 kW | 2000, 2500 kW | 2000 kW |
| Nominal AC voltage | 480–690 V | 480–690 V | 690 V | 690 V | 800 V |
| Grid frequency | 50/60 | 50/60 | 60 | 50/60 | 50/60 |
| DC side | |||||
| DC voltage range | 680–1500 V | 680–1500 V | 1000–1500 V | 1000–1500 V | 1150–1500 V |
| Max DC current | 2182 A | 2650 A | NA | NA | 1952 A |
| Performance | |||||
| Max efficiency | 98.8 % | 98.8 % | NA | NA | 99 % |
| Build | |||||
| Type | NA | NA | NA | NA | NA |
| Cooling | NA | NA | Air | Air | Air |
| Ingress protection | IP66/UL Type 3R | IP55 | NEMA 3R | IP65(PCS) IP54(skid) | IP65 |
| Operating temperature | -20–50 °C | -20–50 °C | -35–60 °C | -35–60 °C | -35–60 °C |
| Weight | about 3500 kg | up to 3000 kg | 13000–14000 kg | 13000–14000 kg | 1500 kg |
| MV transformer built in | No | No | Yes | Yes | No |
| Communication | Ethernet, Modbus (type not stated), Profinet | Modbus TCP | RS485, CAN, Ethernet, Modbus TCP, IEC 61850 | RS485, CAN, Ethernet, Modbus RTU, Modbus TCP, IEC 61850 | RS485, CAN, Ethernet |
| Grid functions | |||||
| Off-grid / black start | Not stated | Not stated | Yes | Yes | Yes |
| Grid-forming | Not stated | Not stated | Yes | Yes | Not stated |
| Certification | |||||
| Certifications | NA | CE, IEC 62477-1, IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-14, IEC 60068-2-30, IEC 61683, EN 50530, IEC 61727, IEC 62116, IEC 62910 | NA | NA | CE, IEC 62477-1, IEC 61000-6-2, IEC 61000-6-4 |
| Source | |||||
| Note | Rated at 25 °C; 1538–2210 kVA at 50 °C. | MV power station (PCS with MV transformer); figures are for the station. The sheet prints the imperial dimensions (19.9×9.5×8.0) as "in"; they are feet. | MV power station (PCS with MV transformer); figures are for the station. | ||
| Model code | PVS980-58BC-1454kVA-E, -1575kVA-F, -1696kVA-G, -1818kVA-I, -1909kVA-J, -2000kVA-K, -2091kVA-L | PVS980-58BC-1738-E, -1883-F, -2028-G, -2173-I, -2282-J, -2390-K, -2500-L | BCS2000K-C-HUD-NP/T2, BCS2500K-C-HUD-NP/T2 | BCS2000K-C-HUD/T2, BCS2500K-C-HUD/T2 | SC2000UD |
| Datasheet | Datasheet (PDF) of FIMER PVS980-58BC-2091kVA-L (opens the maker's site) | Datasheet (PDF) of FIMER PVS980-58BC-2500-L (opens the maker's site) | Spec page of Kehua BCS2000K~2500K-C-HUD-NP/T2 Series (opens the maker's site) | Spec page of Kehua BCS2000K~2500K-C-HUD/T2 Series (opens the maker's site) | Datasheet (PDF) of Sungrow SC2000UD (opens the maker's site) |
| CheckedFigures compared with the maker's sheet | November 2026 | November 2026 | November 2026 | November 2026 | November 2026 |
| Details | Details of FIMER PVS980-58BC-2091kVA-L | Details of FIMER PVS980-58BC-2500-L | Details of Kehua BCS2000K~2500K-C-HUD-NP/T2 Series | Details of Kehua BCS2000K~2500K-C-HUD/T2 Series | Details of Sungrow SC2000UD |
Values as each maker prints them on its own datasheet or spec page, linked in the Datasheet row at the foot of the table; Checked is the date we compared these figures with the maker's sheet. Power and energy are rated figures; a range covers the variants on one sheet. Nothing here is tested by Ingro Energy, and the order is alphabetical by company.
What differs between them
Counted from the 5 products above, as printed.
- Rated power: 1454 to 2500 kW as printed (ranges included)
- DC voltage range: 680 to 1500 V as printed (ranges included)
- Max DC current: 1952 to 2650 A as printed; 2 not published
- Nominal AC voltage: 480 to 800 V as printed (ranges included)
- Grid frequency: 4 50/60, 1 60
- Max efficiency: 98.8 to 99 % as printed; 2 not published
- Cooling: Air; 3 of 5 publish it
- Ingress protection: 5 of 5 publish it; values in the table
- Operating temperature: -35 to 60 °C as printed (ranges included)
- Weight: 1500 to 14000 kg as printed (ranges included) (1 printed as approximate, 1 printed as an upper bound)
- MV transformer built in: 2 of 5
- Off-grid / black start: 3 of 5; 2 not published
- Grid-forming: 2 of 5; 3 not published
- Communication: 5 of 5 publish a list; Ethernet on 4, CAN on 3, Modbus TCP on 3, RS485 on 3
- Certifications: 2 of 5 publish a list; CE on 2, IEC 62477-1 on 2
Nearby power values
A page needs 3+ products from 3+ companies; values without one are in the full list by power.
- 1883 kW1 product
- 1909 kW1 product
- 2091 kW1 product
- 2100 kW1 product
Questions about 2 MW (2000 kW) PCS (power conversion systems)
- Which companies make 2 MW (2000 kW) PCS (power conversion systems) in India?
- 3 companies list 5 products at this size: FIMER (PVS980-58BC-2091kVA-L, PVS980-58BC-2500-L); Kehua (BCS2000K~2500K-C-HUD-NP/T2 Series, BCS2000K~2500K-C-HUD/T2 Series); Sungrow (SC2000UD). They are listed A–Z by company, not ranked.
- How do these 2 MW (2000 kW) PCS (power conversion systems) differ?
- Rated power: 1454 to 2500 kW as printed (ranges included). DC voltage range: 680 to 1500 V as printed (ranges included). Max DC current: 1952 to 2650 A as printed; 2 not published. Nominal AC voltage: 480 to 800 V as printed (ranges included). Counted from the 5 products as each maker prints them.
- Where do these figures come from?
- From each maker's own datasheet or spec page, checked November 2026. Products printed within ±3% of 2000 kW are grouped on this page, each showing its own printed figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with the companies listed.
Is your company on this list? Add it, update your details or raise a concern →