Listed A–Z, not ranked · Reviewed November 2026
Specifications
As printed in the spec page, checked November 2026 (the date we compared these figures with the maker's sheet). NA means not published.
AC side
- Rated power
- 2000–2500 kW
- Printed ratings
- 2000, 2500 kW
- Nominal AC voltage
- 690 V
- Grid frequency
- 60
DC side
- DC voltage range
- 1000–1500 V
- Max DC current
- NA
Performance
- Max efficiency
- NA
Build
- Type
- NA
- Cooling
- Air
- Ingress protection
- NEMA 3R
- Operating temperature
- -35–60 °C
- Weight
- 13000–14000 kg
- MV transformer built in
- Yes
- Communication
- RS485, CAN, Ethernet, Modbus TCP, IEC 61850
Grid functions
- Off-grid / black start
- Yes
- Grid-forming
- Yes
Certification
- Certifications
- NA
- Model code:
- BCS2000K-C-HUD-NP/T2, BCS2500K-C-HUD-NP/T2
- Checked:
- November 2026, against the spec page
Note
MV power station (PCS with MV transformer); figures are for the station. The sheet prints the imperial dimensions (19.9×9.5×8.0) as "in"; they are feet.
Full datasheet
Every row the maker prints, copied as written, read 2026-11-15.
Overview
- Product
- Integrated MV Power Conversion System(digitalenergy.kehua.com)
- Series
- BCS2000K~2500K-C-HUD-NP/T2 Series(digitalenergy.kehua.com)
- Models
- BCS2000K-C-HUD-NP/T2, BCS2500K-C-HUD-NP/T2(digitalenergy.kehua.com)
DC side
- DC voltage range
- 1000-1500Vdc(digitalenergy.kehua.com)
- Max. DC voltage
- 1500Vdc(digitalenergy.kehua.com)
- Max. DC current
- BCS2000K-C-HUD-NP/T2: 1122A*2; BCS2500K-C-HUD-NP/T2: 1403A*2(digitalenergy.kehua.com)
- Soft start
- Yes(digitalenergy.kehua.com)
AC side
- Rated AC power
- BCS2000K-C-HUD-NP/T2: 2000kW; BCS2500K-C-HUD-NP/T2: 2500kW(digitalenergy.kehua.com)
- Max. AC power
- BCS2000K-C-HUD-NP/T2: 2200kVA; BCS2500K-C-HUD-NP/T2: 2750kVA(digitalenergy.kehua.com)
- Nominal AC voltage
- 690Vac 3P3W+PE(digitalenergy.kehua.com)
- AC voltage range
- -15%~10% (settable)(digitalenergy.kehua.com)
- Grid frequency range
- 60Hz(digitalenergy.kehua.com)
- Max. AC current
- BCS2000K-C-HUD-NP/T2: 1841A; BCS2500K-C-HUD-NP/T2: 2301A(digitalenergy.kehua.com)
- Power factor
- >0.99 (at rated power)(digitalenergy.kehua.com)
- Adjustable power factor
- 1 (leading)~1 (lagging)(digitalenergy.kehua.com)
- Current harmonic distortion (THDi)
- <3% (at rated power)(digitalenergy.kehua.com)
Off-grid operation
- Off-grid output voltage
- 690Vac(digitalenergy.kehua.com)
- Off-grid frequency
- 60Hz(digitalenergy.kehua.com)
- Off-grid output current
- BCS2000K-C-HUD-NP/T2: 1841A; BCS2500K-C-HUD-NP/T2: 2301A(digitalenergy.kehua.com)
- Off-grid voltage distortion (THDu)
- <3% (linear load)(digitalenergy.kehua.com)
- Output voltage accuracy
- 1%(digitalenergy.kehua.com)
- Off-grid overload capability
- 110% overload(digitalenergy.kehua.com)
Efficiency
- Max. efficiency
- 99%*(digitalenergy.kehua.com)
MV transformer and switchgear
- MV / LV voltage
- 12~37kV / 0.69kV (can be customized)(digitalenergy.kehua.com)BCS2000K-C-HUD-NP/T2: 10~33kV / 0.69kV (can be customized); BCS2500K-C-HUD-NP/T2: 12~37kV / 0.69kV (can be customized)
- Transformer rated power
- BCS2000K-C-HUD-NP/T2: 4000kVA; BCS2500K-C-HUD-NP/T2: 5000kVA(digitalenergy.kehua.com)
- Transformer isolation
- Oil-immersed transformer(digitalenergy.kehua.com)
Environment
- Operating temperature
- -35ºC~60ºC (>45ºC derating)/-31°F~140°F (>113°F derating)(digitalenergy.kehua.com)
- Relative humidity
- 0~100% (no-condensing)(digitalenergy.kehua.com)
- Max. altitude
- 4000m/9843ft(>2000m/6562ft derating)(digitalenergy.kehua.com)
- Ingress protection
- NEMA 3R(digitalenergy.kehua.com)
- Cooling
- Intelligent air cooling(PCS) KNAN(skid)(digitalenergy.kehua.com)
Physical
- Dimensions (W × H × D)
- 6058×2896×2438mm / 19.9×9.5×8.0in(digitalenergy.kehua.com)
- Weight
- BCS2000K-C-HUD-NP/T2: 13000kg/29762.4lb; BCS2500K-C-HUD-NP/T2: 14000kg/30864.4lb(digitalenergy.kehua.com)
Communication
- Communication
- Modbus-TCP, IEC61850, IEC104(digitalenergy.kehua.com)RS485, CAN, Ethernet(digitalenergy.kehua.com)
- Display / user interface
- LED(digitalenergy.kehua.com)
Features
- Features
- On-line insulation detection(digitalenergy.kehua.com)Designed for extreme environment,such as high temperature(45ºC without derating), salt spray, and extreme cold etc.(digitalenergy.kehua.com)Real-time monitoring of copper bar temperature to ensure machine safety(digitalenergy.kehua.com)Bottom-in, top-out design avoid heat-island effect(digitalenergy.kehua.com)High protection rating (PCS NEMA 4X, skid NEMA 3R) ensures reliable operation in dusty, humid, and saline conditions(digitalenergy.kehua.com)Wide voltage range, supporting flexible battery bank configuration and high-power energy storage(digitalenergy.kehua.com)Support GFM function with millisecond response(digitalenergy.kehua.com)Various applications such as VSG, frequency regulation, black-start, etc.(digitalenergy.kehua.com)High adaptability to the grid with low SCR(digitalenergy.kehua.com)Integrated data acquisition and optical fiber network, simplifying system networking and reducing wiring complexity(digitalenergy.kehua.com)Skid-mounted integrated design of converter and transformer enables integrated delivery, minimizing on-site installation and commissioning time(digitalenergy.kehua.com)On-line insulation detectionAdapt to extreme environment,such as high temperature, salt, and extreme cold etc.Real-time transformer condition monitoringIntegrated design of converter and transformer system, integrated system, Integrated data acquisition and optic fiber networkWide DC voltage operation range, flexible configurationAdapt to multiple scenarios, including power generation side, grid side and user side application, supporting multidevice parallelGrid forming technology, providing extra inertial supportMillisecond-level power response, stable power grid operationMultiple functions, including Black-Start and VSG etc.
Notes
- Notes
- This efficiency value was measured in a laboratory environment.(digitalenergy.kehua.com)Specification indexes may be subject to changes without further notice.(digitalenergy.kehua.com)
More PCS from Kehua
- BCS1000K~1250K-C-HUD
- BCS1000K~1250K-C-HUD-NP
- BCS100K~200K-B-HM X2
- BCS12500K~13800K-C-HUD-EP/T4 Series
- BCS1250K~1725K-B-HUD
- BCS2000K~2500K-C-HUD/T2 Series
- BCS2500K~3450K-B-HUD/T Series
- BCS3150K~3500K-C-HUD-EP
- BCS4000K~5000K-C-HUD-NP/T4
- BCS4000K~5000K-C-HUD/T4 Series
- BCS5000K~6900K-B-HUD/T Series
- BCS500K-S-HLC
Kehua BCS2000K~2500K-C-HUD-NP/T2 Series, in short
The Kehua BCS2000K~2500K-C-HUD-NP/T2 Series is a PCS rated 2000 kW, with cooling Air and MV transformer built in. 4 other PCS at 2000 kW are listed, from 3 makers. Kehua has 15 other PCS on this site.
Same size from other makers: FIMER PVS980-58BC-2091kVA-L, Sungrow SC2000UD, Kehua BCS2000K~2500K-C-HUD/T2 Series, FIMER PVS980-58BC-2500-L · All 2000 kW side by side
Questions about the Kehua BCS2000K~2500K-C-HUD-NP/T2 Series
- What are the main specifications of the Kehua BCS2000K~2500K-C-HUD-NP/T2 Series?
- Rated 2000 kW; Cooling Air; MV transformer built in. As printed on Kehua's spec page (checked November 2026); the full list is on this page.
- Where can I find the Kehua BCS2000K~2500K-C-HUD-NP/T2 Series spec page?
- Kehua publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
- What are the alternatives to the Kehua BCS2000K~2500K-C-HUD-NP/T2 Series?
- Other 2000 kW PCS sold in India include FIMER PVS980-58BC-2091kVA-L, Sungrow SC2000UD, Kehua BCS2000K~2500K-C-HUD/T2 Series and FIMER PVS980-58BC-2500-L. All of them are compared side by side on the 2000 kW page.
- Who makes the Kehua BCS2000K~2500K-C-HUD-NP/T2 Series?
- Kehua, with its head office in Xiamen, China. It has 16 PCS on this site, including this one.
Spot a wrong or outdated figure? Report a correction and we'll check it against the maker's current sheet.
Values as Kehua prints them in the linked spec page; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with Kehua. Product and company names are trademarks of their owners, used only to identify the product.