Listed A–Z, not ranked · Reviewed November 2026
Bidirectional converter, 1738–2500 kVA (IEC version, 2500-L sheet) · PCS by FIMER
Specifications
Datasheet on fimer.com(opens in a new tab)Product pageon fimer.com (opens in a new tab)
As printed in the datasheet, checked November 2026 (the date we compared these figures with the maker's sheet). NA means not published.
AC side
- Rated power
- 1738–2500 kW
- Printed ratings
- 1738, 1883, 2028, 2173, 2282, 2390, 2500 kW
- Nominal AC voltage
- 480–690 V
- Grid frequency
- 50/60
DC side
- DC voltage range
- 680–1500 V
- Max DC current
- 2650 A
Performance
- Max efficiency
- 98.8 %
Build
- Type
- NA
- Cooling
- NA
- Ingress protection
- IP55
- Operating temperature
- -20–50 °C
- Weight
- up to 3000 kg
- MV transformer built in
- No
- Communication
- Modbus TCP
Grid functions
- Off-grid / black start
- Not stated
- Grid-forming
- Not stated
Certification
- Certifications
- CE, IEC 62477-1, IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-14, IEC 60068-2-30, IEC 61683, EN 50530, IEC 61727, IEC 62116, IEC 62910
- Model code:
- PVS980-58BC-1738-E, -1883-F, -2028-G, -2173-I, -2282-J, -2390-K, -2500-L
- Checked:
- November 2026, against the datasheet
Note
Rated at 25 °C; 1538–2210 kVA at 50 °C.
Full datasheet
Every row the maker prints, copied as written, read 2026-11-15.
Overview
- Product
- Bidirectional converterPVS980-58BCPVS980-58BCPVS980-58BC IEC version(fimer.com)
- Models
- PVS980-58BC-1738-E, PVS980-58BC-1883-F, PVS980-58BC-2028-G, PVS980-58BC-2173-I, PVS980-58BC-2282-J, PVS980-58BC-2390-K, PVS980-58BC-2500-L
- Description
- aimed at large-scale grid connected energy storage applicationsbased on the world’s leading converter platform used also in FIMER solar invertersideal for multi-megawatt energy storage systems, providing maximum grid stability for power plants with intermittent energy sources
- Power range
- PVS980-58BC from 1738 to 2500 kVAThe converters are available from 1738 kVA up to 2500 kVA.The converters are available from 869 kVA up to 5000 kVA.(fimer.com)
- Sheet version
- Rev C (file name 'Tech Datasheet_Rev_C')
DC side
- DC voltage range
- PVS980-58BC-1738-E: 680 to 1500 V; PVS980-58BC-1883-F: 737 to 1500 V; PVS980-58BC-2028-G: 794 to 1500 V; PVS980-58BC-2173-I: 850 to 1500 V; PVS980-58BC-2282-J: 893 to 1500 V; PVS980-58BC-2390-K: 935 to 1500 V; PVS980-58BC-2500-L: 978 to 1500 V
- Full-power DC voltage range at 51 °C
- PVS980-58BC-1738-E: 680 to 880 V; PVS980-58BC-1883-F: 737 to 950 V; PVS980-58BC-2028-G: 794 to 1020 V; PVS980-58BC-2173-I: 850 to 1100 V; PVS980-58BC-2282-J: 893 to 1100 V; PVS980-58BC-2390-K: 935 to 1100 V; PVS980-58BC-2500-L: 978 to 1100 V
- Max. DC voltage
- 1500 V
- Max. DC current
- 2650 A
- Max. DC short-circuit current per input
- 73 kApeak, 17 MA2s, external aR fuses required between converter and BESS
- Number of DC inputs
- 10
AC side
- AC power at 25 °C
- PVS980-58BC-1738-E: 1738 kVA; PVS980-58BC-1883-F: 1883 kVA; PVS980-58BC-2028-G: 2028 kVA; PVS980-58BC-2173-I: 2173 kVA; PVS980-58BC-2282-J: 2282 kVA; PVS980-58BC-2390-K: 2390 kVA; PVS980-58BC-2500-L: 2500 kVA
- AC power at 35 °C
- PVS980-58BC-1738-E: 1692 kVA; PVS980-58BC-1883-F: 1833 kVA; PVS980-58BC-2028-G: 1974 kVA; PVS980-58BC-2173-I: 2115 kVA; PVS980-58BC-2282-J: 2220 kVA; PVS980-58BC-2390-K: 2326 kVA; PVS980-58BC-2500-L: 2431 kVA
- AC power at 51 °C
- PVS980-58BC-1738-E: 1538 kVA; PVS980-58BC-1883-F: 1666 kVA; PVS980-58BC-2028-G: 1794 kVA; PVS980-58BC-2173-I: 1922 kVA; PVS980-58BC-2282-J: 2018 kVA; PVS980-58BC-2390-K: 2114 kVA; PVS980-58BC-2500-L: 2210 kVA
- Nominal AC voltage
- PVS980-58BC-1738-E: 480 V; PVS980-58BC-1883-F: 520 V; PVS980-58BC-2028-G: 560 V; PVS980-58BC-2173-I: 600 V; PVS980-58BC-2282-J: 630 V; PVS980-58BC-2390-K: 660 V; PVS980-58BC-2500-L: 690 V
- Grid frequency
- 50/60 Hz
- AC current at 25 °C
- 2091 A
- Max. AC current at 35 °C
- 2035 A
- AC current at 51 °C
- 1850 A
- Max. AC short-circuit current from network
- 66 kA (1s RMS)
- Power factor
- Four quadrants
- Current harmonic distortion (THDi)
- < 3%
- Grid type
- TN and IT
Efficiency
- Max. efficiency
- 98.8%
- European efficiency
- 98.6%
- CEC efficiency
- 98.5%
Grid support
- Grid support
- Reactive power compensation, Power reduction, LVRT, HVRT, FqRT
- Simulation models
- PSS/E; PSCAD; DigSilent
Protection
- Ground fault / insulation monitoring
- Yes
- DC reverse polarity
- Yes
- Short circuit and overcurrent
- Yes
- Overvoltage and overtemperature
- Yes
- Anti-islanding
- Yes
- Grid monitoring
- Yes
Environment
- Operating temperature
- -20 … +50 °C
- Max. ambient temperature
- +60 °C
- Relative humidity
- 4 ... 100%
- Max. altitude
- 4000m Deration to be considered
- Ingress protection
- IP55 Enclosure (IP65 Electronics Section as option)
- Noise
- 84 dBA
Physical
- Dimensions W / H / D (mm)
- 3094/2350/1634
- Weight
- Max. 3000 kg
Auxiliary power
- Own consumption in operation
- 2500 W
- Standby consumption
- 230 W
- Auxiliary supply
- external
Communication
- Communication
- Modbus Ethernet TCP/IP
- Display / user interface
- Local control panel
- Inputs / outputs
- 2/1 as standard, extendable as engineered option7/1 as standard, extendable as engineered option
Certifications
- Certifications and standards
- IEC60068-2-1,-2,-14,-30, IEC61683, EN50530, IEC61727, IEC62116, IEC62910
- Safety standards
- CE Declaration of Conformity, IEC 62477-1
- Grid codes
- IEC
Features
- Features
- High total performance; Modular product design; High DC input voltage up to 1500 VDC; Extensive DC and AC side protection; Easy to commission, no separate chiller installation; Fast and easy AC coupling to transformer by busbars; Versatile design for large-scale plants to minimize system costs; Complete range of industrial data communication options, including remote monitoring; Life cycle service and support through FIMER’s extensive global service networkFIMER bidirectional converters have a high total efficiency. Precise, optimized system control combined with the unit’s highly efficient power converter design deliver the maximum energy from the batteries to the power distribution network.PVS980-58BC converter utilizes patented self-contained cooling system in power module cooling. This innovative, low-maintenance cooling solution is also used in other industrial applications and is designed for demanding environments. The cooling system needs no separate commission and it ensures outstanding endurance.PVS980-58BC converters are designed for fast and easy installation. The industrial design and modular platform provide a wide range of options, such as remote monitoring, fieldbus connection and modular and flexible DC input connections.Equipped with extensive electrical and mechanical protection, the converters are engineered to provide a long and reliable service life of at least 25 years.The PVS980-58BC software includes all the latest grid support and monitoring features, including active power limitation, fault ride through (FRT) with current feed-in and reactive power control. Active and reactive power output can be controlled by an external control system or automatically by the converter. All grid support functions are parameterized. FIMER bidirectional converters are also able to support grid stability at night by providing reactive power with the DC input disconnected.High efficiency; Low auxiliary power consumption; Innovative controlled cooling; Long and reliable service life of at least 25 yearsWater-and dustproof outdoor enclosure; Designed to withstand the toughest environments; Long and reliable service life following the FIMER life cycle modelCompact and easy-to-maintain product design; Fast and easy installation; Integrated and flexible DC input sectionFIMER’s extensive global service network; Extended warranties; Service contracts; Technical support throughout the service lifeSelf-contained, thermosyphon cooled power modules; Liquid-cooled inverter power ratings with the simplicity of air cooling; No fillable liquids, pumps, valves, inhibitors, or leaks; Low maintenanceFast AC connection with AC cable; Integrated DC connection with variable number of inputs; Wide standard option palette for tailoringVery high output power and small footprint allows cost efficient power block designs; 1500 VDC system voltage; Integrated protection to minimize external components.; Fast and easy installation and commissioningComplete range of industrial data communication options for SCADA connections; Ethernet/Internet Protocol; Remote monitoringFIMER supports its customers with a global service network and provides a complete range of life cycle services from installation and commissioning to preventative maintenance, spare parts, repairs and recycling.The modular design allows flexibility to scale up for required the power range (869kVA to 5000kVA). Each individual module will have DC input and AC output section for ease of termination.(fimer.com)Equipped with extensive electrical and mechanical protection, the converters are engineered to provide a long and reliable service life of at least 25 years. The new design allows flexibility to choose bus dust or cable termination on AC connection side.(fimer.com)Active and reactive power output can be controlled by an external control system or automatically by the inverter. All grid support functions are parameterized(fimer.com)High total performance; Comes with optional black start feature; Outstanding endurance for outdoor use; Full four quadrant active power and reactive power support; High DC input voltage up to 1500 VDC for minimizing system cost; Self-contained cooling system suitable for harsh environments; Compact, modular product design; Available with inbuilt DC input fuses; Life cycle service and support through FIMER’s extensive global service network(fimer.com)
- Options and accessories
- Integrated and flexible DC input extension; Heavy duty (Type 1) surge protection; Various internal auxiliary power supply options up to 10kVA for customer use; Floating DC; Fieldbus and Ethernet connections; High altitude version; Low temperature version; Warranty extensions; Bidirectional PCS care contractsIntegrated products, pad mounted- or compact skid solutions; Remote monitoring solutions
- Diagrams
- PVS980-58BC: DC input with fuses and surge protection, converter with Control and Monitor, LCL Filter, AC output with surge protection, transformer
More PCS from FIMER
- PVS980-58BC-1045kVA-LBidirectional converter, 727–1045 kVA (IEC/UL version, 1 MVA sheet)
- PVS980-58BC-1250-LBidirectional converter, 869–1250 kVA (IEC version, 1250-L sheet)
- PVS980-58BC-2091kVA-LBidirectional converter, 1454–2091 kVA (IEC/UL version, 1.6–2.3 MVA sheet)
- PVS980-58BC-3750-LBidirectional converter, 2609–3750 kVA (IEC version, 3750-L sheet)
- PVS980-58BC-5000-LBidirectional converter, 3478–5000 kVA (IEC version, 5000-L sheet)
FIMER PVS980-58BC-2500-L, in short
The FIMER PVS980-58BC-2500-L is a PCS rated 1725 kW, with max efficiency 98.8% and MV transformer built in: no. Its max efficiency (98.8%) is above the median of the 45 PCS listed (98.7%). 4 other PCS at 1725 kW are listed, from 4 makers. FIMER has 5 other PCS on this site.
Same size from other makers: Delta Electronics India PCS1500, Kehua BCS1250K~1725K-B-HUD, Sungrow SC1725UD, FIMER PVS980-58BC-2091kVA-L · All 1725 kW side by side
Questions about the FIMER PVS980-58BC-2500-L
- What are the main specifications of the FIMER PVS980-58BC-2500-L?
- Rated 1725 kW; Max efficiency 98.8%; MV transformer built in: no. As printed on FIMER's datasheet (checked November 2026); the full list is on this page.
- Where can I find the FIMER PVS980-58BC-2500-L datasheet?
- FIMER publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
- What are the alternatives to the FIMER PVS980-58BC-2500-L?
- Other 1725 kW PCS sold in India include Delta Electronics India PCS1500, Kehua BCS1250K~1725K-B-HUD, Sungrow SC1725UD and FIMER PVS980-58BC-2091kVA-L. All of them are compared side by side on the 1725 kW page.
- Who makes the FIMER PVS980-58BC-2500-L?
- FIMER. It has 6 PCS on this site, including this one.
Spot a wrong or outdated figure? Report a correction and we'll check it against the maker's current sheet.
Values as FIMER prints them in the linked datasheet; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with FIMER. Product and company names are trademarks of their owners, used only to identify the product.