Cummins India K19 Series

Listed A–Z, not ranked · Reviewed November 2026

As printed in the datasheet, checked November 2026 (the date we compared these figures with the maker's sheet). NA means not published.

Output

Rating
600–625 kVA
Power output
480–500 kWe
Printed ratings
600, 625 kVA
Rating basis
Prime
Output voltage
415
Frequency
50 Hz
Power factor
0.8 (lagging)
Phase
3-phase

Build

Fuel
Diesel
Engine
Cummins KTAA19-G12 and KTAA19-G13
Alternator
Stamford HCI544E
Enclosure
Acoustic
Dimensions (L × W × H)
6500 × 2010 × 2800 mm (axes not stated)
Fuel tank capacity
832
Weight
about 9029 kg

Certification

CPCB IV+
NA
Certifications and standards
IS/IEC 60034-1, ISO 8528, ISO 3046, IS 1460, ISO 9001, IS 13018

Performance

Governing class
ISO 8528-5 G2
Fuel consumption
98.38 to 102.28 L/h at 75% load
Noise level
75 dBA at 1 m, 75% load, free field

Controls

Controller
Cummins PowerCommand 3.3

Support

Warranty
5 Yrs engine critical parts warranty
Size:
600 kVA
, 625 kVA
Model code:
C600D5P, C625D5P
Checked:
November 2026, against the datasheet

Full datasheet

Every row the maker prints, copied as written, read 2026-11-15.

Overview

Product
Diesel Generator Set K19 Series
Rating
600/625 kVA, 480/500 kWe Prime
Badges and markings
5 YRS ENGINE CRITICAL PARTS WARRANTYCPCB II COMPLIANT · ENVIRONMENT FRIENDLY
Sheet reference
PSBU/026/K19-600-625kVA/Revision-5/ (02-2023)

Ratings

Model
C600D5P: C600D5P; C625D5P: C625D5P
Duty
Prime
Power rating (kVA / kWe)
C600D5P: 600/480; C625D5P: 625/500
Prime power definition
Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528.
Phases
3
Output voltage and frequency (V, Hz)
415 V, 50 Hz
Power factor
0.8 (lagging)
Current (A)
C600D5P: 835; C625D5P: 870
Speed (RPM)
1500

Engine

Engine make
Cummins®
Engine model
C600D5P: KTAA19-G12; C625D5P: KTAA19-G13
MoEF certified power (bhp)
C600D5P: 713; C625D5P: 739
Power required for rated kVA (bhp)
C600D5P: 708; C625D5P: 734
Cooling
Liquid Cooled (EG Compleat 50:50)
Aspiration
Turbocharged, Charge air Cooled
Cylinders
6, In-line
Bore × stroke (mm)
159 x 159
Displacement (litre)
19
Compression ratio
14.3:1
Mean piston speed (m/s)
7.95
Governor / performance class
ISO 8528-5 G2
Starting system
24 V DC Electrical
Lube oil specification
15W40 API, CI4+
Lube oil sump capacity, high–low (litre)
38-32
Lubrication system capacity (litre)
50
Coolant capacity (litre)
90
Combustion air intake at 100% load, ±5% (cfm)
C600D5P: 1458; C625D5P: 1496
Exhaust temperature (°C)
527
Exhaust pipe size (inch)
10
Engine wet weight, engine + radiator (kg)
2500
Engine L × W × H (mm)
1830 x 964 x 1514
Engine features
Cummins® K19 series, 6 cylinder, In-line, 4 stroke, radiator cooled engineHighly stable and reliable design with square engineWell designed air handling system with: Dry type, replaceable paper element air cleaner with restriction indicatorWell designed air handling system with: Optimised turbocharger for increased altitude capabilitiesWell designed air handling system with: Air to air aftercoolingBest in class fuel economy with: PT fuel system with Electronic Step Timing Control (ESTC) injectors which smoothly stabilise engine speed under load with Electronic governingBest in class fuel economy with: Dual fuel filter system: Pre filter including water separator and Water In Fuel (WIF) sensor and main filterStandard integral set-mounted radiator system, designed and tested for 50°C ambient temperatureVenturi combo Spin on oil filterPlate type lube oil coolerFirst fill of lube oil and CoolantElectrical starter motor with soft start engagement featureBattery charging alternator2x12 V DC Batteries

Fuel

Fuel
High Speed Diesel
Fuel consumption at 75% load (litre/hr)
C600D5P: 98.38; C625D5P: 102.28
Fuel consumption at 100% load (litre/hr)
C600D5P: 125.5; C625D5P: 129.74
Standard fuel tank capacity (litre)
832

Alternator

Alternator make
Stamford (CGT)
Alternator frame
HCI544E
Alternator enclosure
IP 23
Voltage regulation
±1%
Insulation class
H Class
Winding pitch
2/3
Stator winding
Double layer lap
Rotor
Dynamically Balanced
Total harmonic distortion
No load < 1.5 %, Non distorting balanced linear load < 5 %
Maximum unbalanced load across phases
less than or equal to 25%
Telephone harmonic factor
< 2%
Alternator features
Stamford HC alternator frame from Cummins Generator TechnologiesBrushless Type, Screen protected, Revolving field, Self excited Alternator conforming to IS/IEC 60034-13 Phase reconnectable winding with 12 terminals brought out for connectionBetter motor starting capabilityBest in class efficiencyCompact design with sealed bearings for longer life and lesser maintenanceImpregnation on all wound components for better mechanical strength

Controls

Controller description
The PowerCommand® control system is an integrated microprocessor-based generator set monitoring, metering and control system with LCD display designed to meet the demands of today's engine driven generator sets. temperature, Low coolant level, Oil temperature, Intake manifold temperature, Battery voltage, Engine speed
Control panel
Control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish.PowerCommand® 3.3 ControllerAluminum bus bars with suitable capacity with incoming/ outgoing terminalsIndicating lamps for 'Load ON' and 'Set Running'Instrument fuses duly wired and ferruledAir Circuit Breakers (ACBs) of suitable rating with overload and short circuit protectionsIntuitive operator interface which includes LED backlit LCD display with tactile feel soft-switches & generator set status LED lampsIntegrated digital electronic voltage regulator with configurable torque matching.Digital Electronic Governing with temperature compensation and Smart Starting.SAE J1939 Interface to Full Authority Electronic (FAE) engines.Remote Start-StopEngine Metering: Oil pressure, High/ Low coolant
Alternator metering
L-L Voltage and L-N Voltage, Current (1 and 3 phase), kW, kVAR, Power factor, kVA (three phase and total), and Frequency.
Utility / AC bus metering
L-L Voltage and L-N Voltage, Current (1 and 3 phase), kW, kVAR, Power factor, kVA (three phase and total), and Frequency.
Engine protection
Low lube oil pressure, High / Low coolant temperature, Over speed, Battery Over / Under/ Weak Volts, Fail to crank / start, Cranking lockout, Low fuel level, Sensor failure.
Alternator protection
AmpSentry protective relays for short circuit shutdown, Over / Under voltage, Over / Under frequency, Over current, Overload, Reverse power, Reverse VAr, Phase rotation and Loss of AC sensing.
Utility / AC bus protection
Over / Under voltage, Under frequency and Phase rotation
Data logging
Genset model data, Engine hours, Control hours, Engine starts, Load profile, kWh and upto 32 recent fault codes
Control functions
Start-stop with configurable time delay, Real time clock for fault and event time stamping, Exerciser clock and time of day start/ stop, Configurable glow plug control, Configurable cycle cranking, Load shed / dump as per configurable priority
Paralleling
Digital frequency synchronization and voltage matching, Isochronous kW and kVAr load sharing controls, Droop kW and kVAr control, Sync check, Extended paralleling (Peak Shave / Base Load), Digital power transfer control (AMF), Load govern control, Load demand control
Controller certifications
meets the requirement of relevant UL, NFPA, ISO, IEC, Mil Std., CE and CSA standards
Controller features
Paralleling protections12 and 24 Volt DC OperationSleep ModeProgrammable I/Os (4 inputs and 4 outputs), expandablewith AUX101/102 modulesSelf-Configuring PCCNet networkModbus Interface (RS485 RTU)InPower Compatible (PC based service tool)
Remote monitoring / telematics
Fault Code Alerts on Email & SMSAdvisory ServicesFuel Level Monitoring on Email & SMSMultiple Gensets Central MonitoringAutomatic Reports Generation

Enclosure & acoustics

Enclosure
SilentPower
Acoustic enclosure
Specially designed to meet stringent MoEF/ CPCB norms of 75 dBA @ 1mtr at 75% load under free field conditionsThe acoustic enclosure is made of CRCA sheets in Munsell green shade and a structural/ sheet metal base frame painted in blackHigh quality noise absorbant and fire-retardant grade acoustic insulation material (Rockwool) complying to IS 8183Base lifting for easy handling at customer siteDesigned to have optimum serviceabilityAir inlet louvers specially designed to operate at rated loadMade on special purpose CNC machines for consistency in quality and workmanship11 tank pretreatment process and UV resistant powder coating of all parts to withstand extreme environmentUse of special hardware for longer lifeFlush styling - no projectionsFluid drains for lube oil and fuelFuel filling arrangement inside the enclosure
Silencer
Hospital grade silencer suitably optimised to meet stringent noise emission standards laid down by MoEF/CPCB

Physical

Length (mm)
6500
Width (mm)
2010
Height (mm)
2800
Wet weight (kg)
9029
Mounting arrangement
Engine and alternator are mounted on a common MS fabricated base frame with AVM pads.Base frame with integral fuel tank is provided with drain plug, air vent, inlet and outlet connection, level indicator and provision for cleaning

Options

Optional: engine
Coolant heater, Heat exchanger, No cool, Remote radiator
Optional: alternator
PMG
Optional: control panel
Microprocessor / relay based AMF control panel
Optional: other
Trolley mounted mobile sets

Certifications

Conformance standards
IS/IEC 60034-1, IS 1460, ISO 8528, ISO 3046, ISO 9001, IS 13018

Features

Highlights
The Cummins® K19 series heavy-duty engine and world class Stamford alternator powered diesel generator setProven technology with mechanical simplicity of Cummins® PT fuel systemAdvanced in-cylinder technology to meet latest emission norms without any after-treatment deviceSmart aesthetic and superior finishCompact in size with optimum power to weight ratioHighly reliable and durable productAll elements are designed to work together to maximize efficiency even at part loads, offering the advantage of lowest operating costs500Hours or 1 year service interval, whichever is earlierIndustry acknowledged best-in-class comprehensive warranty on the entire package including rubber componentsClass defining technology engine is designed to meet stringent exhaust emission tests as per revised MoEF norms, thus offering environment friendly powerThe Cummins® diesel generator sets are available with the lowest noise levels in its rangeAll the major components - the engine, alternator, control system and canopy are designed, manufactured and tested by Cummins IndiaBest and largest customer support network in India, capable of providing round-the-clock service and spares supportAll these things put together, Cummins® offers you the SINGLE SOURCE POWER ASSURANCE

Notes

Sheet footnotes
Fuel consumption data is based on diesel having specific gravity of 0.85 and conforming to IS:1460. Fuel consumption tolerance is +5%With the condition that none of the phases exceeds its rated currentApproximate Weight

More DG sets from Cummins India

Cummins India K19 Series, in short

The Cummins India K19 Series is a DG set rated 600 kVA, with rating basis Prime and fuel Diesel. 1 other DG set at 600 kVA is listed, from 1 maker. Cummins India has 8 other DG sets on this site.

Same size from other makers: Sudhir Power CS D5P series

Questions about the Cummins India K19 Series

What are the main specifications of the Cummins India K19 Series?
Rated 600 kVA; Rating basis Prime; Fuel Diesel. As printed on Cummins India's datasheet (checked November 2026); the full list is on this page.
Where can I find the Cummins India K19 Series datasheet?
Cummins India publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
What are the alternatives to the Cummins India K19 Series?
Other 600 kVA DG sets sold in India include Sudhir Power CS D5P series.
Who makes the Cummins India K19 Series?
Cummins India, with its head office in Pune. It has 9 DG sets on this site, including this one.

Spot a wrong or outdated figure? Report a correction and we'll check it against the maker's current sheet.

Values as Cummins India prints them in the linked datasheet; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with Cummins India. Product and company names are trademarks of their owners, used only to identify the product.

Not sure what to buy? Ask us what's compatible and what size fits your site.