Listed A–Z, not ranked · Reviewed November 2026
Specifications
As printed in the spec page, checked November 2026 (the date we compared these figures with the maker's sheet). NA means not published.
AC side
- Rated power
- 1250–1725 kW
- Printed ratings
- 1250, 1500, 1725 kW
- Nominal AC voltage
- 690 V
- Grid frequency
- 50/60
DC side
- DC voltage range
- 1000–1500 V
- Max DC current
- 1936 A
Performance
- Max efficiency
- 99 %
Build
- Type
- Central
- Cooling
- Air
- Ingress protection
- IP55
- Operating temperature
- -35–60 °C
- Weight
- 1580 kg
- MV transformer built in
- No
- Communication
- RS485, Ethernet, Modbus RTU, Modbus TCP, IEC 61850
Grid functions
- Off-grid / black start
- Yes
- Grid-forming
- Yes
Certification
- Certifications
- IEC EN 62477-1, EN IEC 61000-6-2/4, EN 50549-2/10, IEC 60068-2-1/2/14/30, EN 55011
- Model code:
- BCS1250K-B-HUD, BCS1500K-B-HUD, BCS1725K-B-HUD
- Checked:
- November 2026, against the spec page
Full datasheet
Every row the maker prints, copied as written, read 2026-11-15.
Overview
- Product
- 1500Vdc Energy Storage Converter(digitalenergy.kehua.com)
- Series
- BCS1250K~1725K-B-HUD Series(digitalenergy.kehua.com)
- Models
- BCS1250K-B-HUD, BCS1500K-B-HUD, BCS1725K-B-HUD(digitalenergy.kehua.com)
- Topology
- None(digitalenergy.kehua.com)
DC side
- DC voltage range
- 1000-1500Vdc(digitalenergy.kehua.com)
- Max. DC voltage
- 1500Vdc(digitalenergy.kehua.com)
- Max. DC current
- BCS1250K-B-HUD: 1403A; BCS1500K-B-HUD: 1683A; BCS1725K-B-HUD: 1936A(digitalenergy.kehua.com)
- Soft start
- Yes(digitalenergy.kehua.com)
AC side
- Rated AC power
- BCS1250K-B-HUD: 1250kW; BCS1500K-B-HUD: 1500kW; BCS1725K-B-HUD: 1725kW(digitalenergy.kehua.com)
- Max. AC power
- BCS1250K-B-HUD: 1375kVA; BCS1500K-B-HUD: 1650kVA; BCS1725K-B-HUD: 1897.5kVA(digitalenergy.kehua.com)
- Nominal AC voltage
- 690Vac 3P3W+PE(digitalenergy.kehua.com)
- AC voltage range
- -15%~10% (settable)(digitalenergy.kehua.com)
- Grid frequency range
- 50/60Hz(digitalenergy.kehua.com)
- Max. AC current
- BCS1250K-B-HUD: 1151A; BCS1500K-B-HUD: 1381A; BCS1725K-B-HUD: 1588A(digitalenergy.kehua.com)
- Power factor
- >0.99 (at rated power)(digitalenergy.kehua.com)
- Adjustable power factor
- 1 (leading)~1 (lagging)(digitalenergy.kehua.com)
- Current harmonic distortion (THDi)
- <3% (at rated power)(digitalenergy.kehua.com)
Off-grid operation
- Off-grid output voltage
- 690Vac(digitalenergy.kehua.com)
- Off-grid frequency
- 50/60Hz(digitalenergy.kehua.com)
- Off-grid output current
- BCS1250K-B-HUD: 1151A; BCS1500K-B-HUD: 1381A; BCS1725K-B-HUD: 1588A(digitalenergy.kehua.com)
- Off-grid voltage distortion (THDu)
- <3% (linear load)(digitalenergy.kehua.com)
- Output voltage accuracy
- 1%(digitalenergy.kehua.com)
- Off-grid overload capability
- 110% overload(digitalenergy.kehua.com)
Efficiency
- Max. efficiency
- 99%*(digitalenergy.kehua.com)
Environment
- Operating temperature
- -35ºC~60ºC (>50ºC derating)(digitalenergy.kehua.com)
- Relative humidity
- 0~100% (no-condensing)(digitalenergy.kehua.com)
- Max. altitude
- 4000m (>2000m derating)(digitalenergy.kehua.com)
- Ingress protection
- IP55(digitalenergy.kehua.com)
- Cooling
- Intelligent air cooling(digitalenergy.kehua.com)
Physical
- Dimensions (W × H × D)
- 860×2270×1909mm(digitalenergy.kehua.com)
- Weight
- 1580kg(digitalenergy.kehua.com)
Communication
- Communication
- Modbus-RTU, Modbus-TCP, IEC61850, IEC104(digitalenergy.kehua.com)RS485, Ethernet(digitalenergy.kehua.com)
- Display / user interface
- Touch screen(digitalenergy.kehua.com)
Certifications
- Certifications and standards
- IEC EN 62477-1, EN IEC 61000-6-2/4, EN 50549-2/10, IEC 60068-2-1/2/14/30, EN 55011(digitalenergy.kehua.com)
Features
- Features
- On-line insulation detection(digitalenergy.kehua.com)Designed for extreme environment,such as high temperature (50ºC without derating), salt spray, and extreme cold etc.(digitalenergy.kehua.com)Maximum efficiency up to 99%, minimizing energy loss during conversion(digitalenergy.kehua.com)Noise ≤ 75dBA with full-load operation(digitalenergy.kehua.com)Support GFM function with millisecond response(digitalenergy.kehua.com)Various applications such as VSG, frequency regulation, black-start, etc.(digitalenergy.kehua.com)High adaptability to the grid with low SCR(digitalenergy.kehua.com)Power unit is modularly designed and easy to maintain.(digitalenergy.kehua.com)Multiple communication interfaces (RS485, Ethernet) enable remote O&M and data acquisition(digitalenergy.kehua.com)Intelligent air cooling with adaptive fan control, reducing energy consumption and maintenance frequency(digitalenergy.kehua.com)Adapt to extreme environment,such as high temperature(50ºC without derating), salt, and extreme cold etc.Noise ≤ 75dBA, better protecting the hearing of operation and maintenance personnelEfficient layout to improve space utilizationSecondary circuit integration, unified measurement, protection and communicationSupport multi-machine parallel connection & black startH/LVRT function, high adaptation ability to the gridVarious applications such as peak shaving, frequency modulation, auxiliary grid connection for new energy system, etc
Notes
- Notes
- This efficiency value was measured in a laboratory environment.(digitalenergy.kehua.com)Specification indexes may be subject to changes without further notice.(digitalenergy.kehua.com)
More PCS from Kehua
- BCS1000K~1250K-C-HUD
- BCS1000K~1250K-C-HUD-NP
- BCS100K~200K-B-HM X2
- BCS12500K~13800K-C-HUD-EP/T4 Series
- BCS2000K~2500K-C-HUD-NP/T2 Series
- BCS2000K~2500K-C-HUD/T2 Series
- BCS2500K~3450K-B-HUD/T Series
- BCS3150K~3500K-C-HUD-EP
- BCS4000K~5000K-C-HUD-NP/T4
- BCS4000K~5000K-C-HUD/T4 Series
- BCS5000K~6900K-B-HUD/T Series
- BCS500K-S-HLC
Kehua BCS1250K~1725K-B-HUD, in short
The Kehua BCS1250K~1725K-B-HUD is a PCS rated 1250 kW, with max efficiency 99%, cooling Air and MV transformer built in: no. Its max efficiency (99%) is above the median of the 45 PCS listed (98.7%). 3 other PCS at 1250 kW are listed, from 2 makers. Kehua has 15 other PCS on this site.
Same size from other makers: FIMER PVS980-58BC-1250-L, Kehua BCS1000K~1250K-C-HUD, Kehua BCS1000K~1250K-C-HUD-NP
Questions about the Kehua BCS1250K~1725K-B-HUD
- What are the main specifications of the Kehua BCS1250K~1725K-B-HUD?
- Rated 1250 kW; Max efficiency 99%; Cooling Air; MV transformer built in: no. As printed on Kehua's spec page (checked November 2026); the full list is on this page.
- Where can I find the Kehua BCS1250K~1725K-B-HUD spec page?
- Kehua publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
- What are the alternatives to the Kehua BCS1250K~1725K-B-HUD?
- Other 1250 kW PCS sold in India include FIMER PVS980-58BC-1250-L, Kehua BCS1000K~1250K-C-HUD and Kehua BCS1000K~1250K-C-HUD-NP.
- Who makes the Kehua BCS1250K~1725K-B-HUD?
- Kehua, with its head office in Xiamen, China. It has 16 PCS on this site, including this one.
Spot a wrong or outdated figure? Report a correction and we'll check it against the maker's current sheet.
Values as Kehua prints them in the linked spec page; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with Kehua. Product and company names are trademarks of their owners, used only to identify the product.