Power Electronics Freemaq Multi PCSK

Listed A–Z, not ranked · Reviewed November 2026

Battery inverter with 2–4 separate DC inputs, 480–690 V AC (sheet V. 1.4.5) · PCS by Power ElectronicsLegacy

As printed in the datasheet, checked November 2026 (the date we compared these figures with the maker's sheet). NA means not published.

AC side

Rated power
1525–4390 kW
Printed ratings
1525, 1590, 1685, 1910, 1955, 2005, 2055, 2100, 2195, 2290, 2385, 2530, 2865, 2935, 3005, 3055, 3080, 3150, 3180, 3290, 3370, 3820, 3915, 4010, 4105, 4200, 4390 kW
Nominal AC voltage
480–690 V
Grid frequency
50/60

DC side

DC voltage range
679–1500 V
Max DC current
NA

Performance

Max efficiency
98.95 %

Build

Type
NA
Cooling
Air
Ingress protection
NEMA 3R / IP55
Operating temperature
-40–60 °C
Weight
3900–4700 kg
MV transformer built in
No
Communication
Modbus TCP

Grid functions

Off-grid / black start
Not stated
Grid-forming
Not stated

Certification

Certifications
UL 1741, CSA 22.2 No.107.1-16, IEC 62109-1, IEC 62109-2, IEC 62477-1, IEEE 1547, UL 1741 SA & SB, IEC 62116
Size:
22 sizes
Model code:
FP2195K2, FP3290K3, FP4390K2, FP4390K4 (and the matching K2/K3/K4 codes for 660, 645, 630, 615, 600, 530, 500 and 480 V)
Checked:
November 2026, against the datasheet

Full datasheet

Every row the maker prints, copied as written, read 2026-11-15.

Overview

Product
Freemaq Multi PCSK
Models
690 V frame 2 / frame 3 / frame 4: FP2195K2 / FP3290K3 / FP4390K2 / FP4390K4; 660 V frame 2 / frame 3 / frame 4: FP2101K2 / FP3151K3 / FP4200K2 / FP4200K4; 645 V frame 2 / frame 3 / frame 4: FP2055K2 / FP3080K3 / FP4105K2 / FP4105K4; 630 V frame 2 / frame 3 / frame 4: FP2005K2 / FP3005K3 / FP4010K2 / FP4010K4; 615 V frame 2 / frame 3 / frame 4: FP1955K2 / FP2935K3 / FP3915K2 / FP3915K4; 600 V frame 2 / frame 3 / frame 4: FP1910K2 / FP2865K3 / FP3820K2 / FP3820K4; 530 V frame 2 / frame 3 / frame 4: FP1685K2 / FP2530K3 / FP3370K2 / FP3370K4; 500 V frame 2 / frame 3 / frame 4: FP1590K2 / FP2385K3 / FP3180K2 / FP3180K4; 480 V frame 2 / frame 3 / frame 4: FP1525K2 / FP2290K3 / FP3055K2 / FP3055K4
Description
OUR PCSK are battery inverters for utility-scale applications.(power-electronics.com)The utility-scale battery inverters. From one independent BESS with PCSK to up to four independent BESS with Multi PCSK.(bucket-software00.s3.eu-west-1.amazonaws.com)
Power range
Up to 5360 kVA(power-electronics.com)
Battery type
All type of batteries (BMS required)
Sheet version
V. 1.4.5 20260828

DC side

DC voltage range
690 V: 976 V - 1500 V; 660 V: 934 V - 1500 V; 645 V: 913 V - 1500 V; 630 V: 891 V - 1500 V; 615 V: 870 V - 1500 V; 600 V: 849 V - 1500 V; 530 V: 750 V - 1500 V; 500 V: 708 V - 1500 V; 480 V: 679 V - 1500 VUp to 1500 Vdc(power-electronics.com)
Max. DC voltage
1500 V
DC voltage windows
Nine different DC voltage windows(power-electronics.com)
Max. DC continuous current per input (A)
Frame 2: 1148; Frame 3: 1148; Frame 4 (…K2): 2295; Frame 4 (…K4): 1148
Max. DC short-circuit current per input
500 kA with a time constant of 1 ms
DC voltage ripple
<3%
Number of DC inputs
Frame 2 (…K2): 2; Frame 3 (…K3): 3; Frame 4 (…K2): 2; Frame 4 (…K4): 4Frame 2: 2; Frame 3: 3; Frame 4: 2 / 4

AC side

AC output power at 40 °C (kVA/kW)
FP2195K2: 2195; FP3290K3: 3290; FP4390K2/FP4390K4: 4390; FP2101K2: 2100; FP3151K3: 3150; FP4200K2/FP4200K4: 4200; FP2055K2: 2055; FP3080K3: 3080; FP4105K2/FP4105K4: 4105; FP2005K2: 2005; FP3005K3: 3005; FP4010K2/FP4010K4: 4010; FP1955K2: 1955; FP2935K3: 2935; FP3915K2/FP3915K4: 3915; FP1910K2: 1910; FP2865K3: 2865; FP3820K2/FP3820K4: 3820; FP1685K2: 1685; FP2530K3: 2530; FP3370K2/FP3370K4: 3370; FP1590K2: 1590; FP2385K3: 2385; FP3180K2/FP3180K4: 3180; FP1525K2: 1525; FP2290K3: 2290; FP3055K2/FP3055K4: 3055
AC output power at 50 °C (kVA/kW)
FP2195K2: 2035; FP3290K3: 3055; FP4390K2/FP4390K4: 4075; FP2101K2: 1950; FP3151K3: 2925; FP4200K2/FP4200K4: 3900; FP2055K2: 1905; FP3080K3: 2855; FP4105K2/FP4105K4: 3810; FP2005K2: 1860; FP3005K3: 2790; FP4010K2/FP4010K4: 3720; FP1955K2: 1815; FP2935K3: 2725; FP3915K2/FP3915K4: 3635; FP1910K2: 1775; FP2865K3: 2660; FP3820K2/FP3820K4: 3545; FP1685K2: 1565; FP2530K3: 2350; FP3370K2/FP3370K4: 3130; FP1590K2: 1475; FP2385K3: 2215; FP3180K2/FP3180K4: 2955; FP1525K2: 1415; FP2290K3: 2125; FP3055K2/FP3055K4: 2840
Nominal AC voltage (V)
690 V: 690 V ±10%; 660 V: 660 V ±10%; 645 V: 645 V ±10%; 630 V: 630 V ±10%; 615 V: 615 V ±10%; 600 V: 600 V ±10%; 530 V: 530 V ±10%; 500 V: 500 V ±10%; 480 V: 480 V ±10%
Grid frequency
50/60 Hz
Max. AC output current at 40 °C (A)
Frame 2: 1837; Frame 3: 2756; Frame 4: 3674
Power factor
0.5 leading… 0.5 lagging
Reactive power
Four quadrant operation
Current harmonic distortion (THDi)
<3% per IEEE519
Overload capability
166% - 100 ms / 150% - 5 s / 120% - 8 s / 110% - 15 s

Efficiency

Max. efficiency
FP2195K2: 98.84%; FP3290K3: 98.87%; FP4390K2/FP4390K4: 98.94%; FP2101K2: 98.86%; FP3151K3: 98.89%; FP4200K2/FP4200K4: 98.95%; FP2055K2: 98.85%; FP3080K3: 98.88%; FP4105K2/FP4105K4: 98.81%; FP2005K2: 98.79%; FP3005K3: 98.82%; FP4010K2/FP4010K4: 98.88%; FP1955K2: 98.75%; FP2935K3: 98.78%; FP3915K2/FP3915K4: 98.77%; FP1910K2: 98.82%; FP2865K3: 98.85%; FP3820K2/FP3820K4: 98.78%; 530 V (all references): 98.78% (preliminary); 500 V (all references): 98.78% (preliminary); 480 V (all references): 98.78% (preliminary)
European efficiency
FP2195K2: 98.34%; FP3290K3: 98.49%; FP4390K2/FP4390K4: 98.51%; FP2101K2: 98.36%; FP3151K3: 98.51%; FP4200K2/FP4200K4: 98.53%; FP2055K2: 98.24%; FP3080K3: 98.39%; FP4105K2/FP4105K4: 98.41%; FP2005K2: 98.28%; FP3005K3: 98.43%; FP4010K2/FP4010K4: 98.45%; FP1955K2: 98.20%; FP2935K3: 98.35%; FP3915K2/FP3915K4: 98.37%; FP1910K2: 98.18%; FP2865K3: 98.33%; FP3820K2/FP3820K4: 98.35%; 530 V (all references): 98.35% (preliminary); 500 V (all references): 98.35% (preliminary); 480 V (all references): 98.35% (preliminary)

Protection

DC protection and disconnection
High-speed fuses, Motorized DC disconnect switches
AC protection and disconnection
Circuit breaker
Overvoltage protection
Type II for AC and Type I+II for DC
Ground fault / insulation monitoring
Insulation monitoring device
Humidity control
Active heating

Environment

Operating temperature
From -40 °C to +60 °C, >40 °C power derating
Storage temperature
From -40 °C to +60 °C
Relative humidity
From 4% to 100%
Max. altitude
2000m / >2000m power derating (Max. 4000m)
Ingress protection
NEMA 3R / IP55
Cooling
Forced air cooling

Physical

Dimensions W × D × H (m)
3.0 x 2.0 x 2.3
Dimensions W × D × H (ft)
9.8 x 6.5 x 7.5
Weight
Frame 2: 8600; Frame 3: 9700; Frame 4: 10365Frame 2: 3900; Frame 3: 4400; Frame 4: 4700

Communication

Communication
Modbus TCP
Display / user interface
Standard
Power plant controller
Optional. Third party SCADA systems supported

Certifications

Safety standards
UL 1741 / CSA 22.2 No.107.1-16 / IEC 62109-1 / IEC 62109-2 / IEC 62477-1
Grid codes
IEEE 1547:2018 / UL 1741 SA & SB/ IEC 62116:2014
Installation standard
NEC 2023

Features

Features
This product provides advanced grid support capabilities, enabling up to 4* Battery Energy Storage Systems (BESS) to operate simultaneously. It also offers up to nine voltage levels to suit any battery technology. *Only available with Multi PCSK.(power-electronics.com)It offers the advantages of a central inverter with the modularity of string inverters.(power-electronics.com)Designed for easy field maintenance, with up to four FRUs (Field Replaceable Units).(power-electronics.com)It enables higher battery capacity by providing up to four times the short-circuit withstand of single DC input systems. Multiple power references allow for independent control of each BESS. Furthermore, it offers greater availability, as a battery fault only affects the corresponding power modules within the system.(power-electronics.com)Modularity. / Easy maintenance. / Up to 4 independent DC inputs. / Advanced grid support. / Compatible with all battery technologies.Designed for easy on-site replacement, with a safe, reliable, and fast plug-and-play assembly system. Includes up to four FRUs (Field Replaceable Units).(bucket-software00.s3.eu-west-1.amazonaws.com)Enables DC power redistribution when one module fails. Lower energy losses = higher availability and efficiency.(bucket-software00.s3.eu-west-1.amazonaws.com)Capable of operating on any power system, with different modes depending on the application: grid-forming or grid-following.(bucket-software00.s3.eu-west-1.amazonaws.com)The three-level IGBT topology reduces power-stage losses, increases inverter efficiency, and minimizes total harmonic distortion—achieving high efficiency for the lowest levelized cost of energy (LCOE).(bucket-software00.s3.eu-west-1.amazonaws.com)Choose your model based on your specific requirements.(bucket-software00.s3.eu-west-1.amazonaws.com)Maximum power up to 1500 V / Up to 5360 kVA / Ten different voltage DC windows / Full grid support capability / Grid-forming capability / *Up to four independent BESS (*Only Multi PCSK)(bucket-software00.s3.eu-west-1.amazonaws.com)Higher battery capacity thanks to the short-circuit withstand capability of each DC input. Up to four times more than a single input. / Multiple power references allow independent BESS control. / Higher availability since a battery fault will only remove the affected power modules from the system. (Only Multi PCSK)(bucket-software00.s3.eu-west-1.amazonaws.com)

Notes

Notes
Values at 1.00·Vac nom and CosPhi=1. The maximum AC output power must be limited to meet the P-Q capability requirement at the inverter level of some grid codes. Consult Power Electronics for derating curves.Consult Power Electronics for derating curves. In the event of overvoltage in the grid, the minimum DC voltage will vary proportionally with the AC voltage.Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).Optional available for temperatures below -25 ºC.Battery short circuit disconnection has to be done on the battery side.Consult Power Electronics for other applicable standards/grid codes.Available from January 2027.

More PCS from Power Electronics

  • Freemaq Multi PCSKBattery inverter with 2 or 4 separate DC inputs, 690 V AC (Gen3 sheet V. 2.0.5)
  • Freemaq Multi PCSKBattery inverter with 2 or 4 separate DC inputs, 720 V AC (Gen3 sheet V. 2.0.5)
  • Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 33/34.5 kV, IEC (sheet V. 1.4.4)
  • Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 20–34.5 kV, 690 V PCS, IEC (Gen3 sheet V. 2.0.5)
  • Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 20–34.5 kV, 720 V PCS, IEC (Gen3 sheet V. 2.0.5)
  • Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 33 kV, 690 V PCS, IEC (Gen3 sheet V. 3.0.0, preliminary)
  • Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 33 kV, 720 V PCS, IEC (Gen3 sheet V. 3.0.0, preliminary)
  • Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 12.47–34.5 kV, UL (sheet V. 1.4.4)
  • Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 690 V PCS, UL (Gen3 sheet V. 2.0.4)
  • Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 720 V PCS, UL (Gen3 sheet V. 2.0.4)
  • Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 690 V PCS, UL (Gen3 sheet V. 3.0.0, preliminary)
  • Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 720 V PCS, UL (Gen3 sheet V. 3.0.0, preliminary)
All 26 on the Power Electronics profile

Power Electronics Freemaq Multi PCSK, in short

The Power Electronics Freemaq Multi PCSK is a PCS rated 1500 kW, with max efficiency 98.95%, cooling Air and MV transformer built in: no. Its max efficiency (98.95%) is above the median of the 45 PCS listed (98.7%). Power Electronics has 25 other PCS on this site.

Questions about the Power Electronics Freemaq Multi PCSK

What are the main specifications of the Power Electronics Freemaq Multi PCSK?
Rated 1500 kW; Max efficiency 98.95%; Cooling Air; MV transformer built in: no. As printed on Power Electronics' datasheet (checked November 2026); the full list is on this page.
Where can I find the Power Electronics Freemaq Multi PCSK datasheet?
Power Electronics publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
Who makes the Power Electronics Freemaq Multi PCSK?
Power Electronics, with its head office in Valencia, Spain. It has 26 PCS on this site, including this one.

Spot a wrong or outdated figure? Report a correction and we'll check it against the maker's current sheet.

Values as Power Electronics prints them in the linked datasheet; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with Power Electronics. Product and company names are trademarks of their owners, used only to identify the product.

Not sure what to buy? Ask us what's compatible and what size fits your site.