Listed A–Z, not ranked · Reviewed November 2026
Battery inverter with 2 or 4 separate DC inputs, 690 V AC (Gen3 sheet V. 2.0.5) · PCS by Power Electronics
Specifications
Datasheet on bucket-software00.s3.amazonaws.com(opens in a new tab)Product pageon power-electronics.com (opens in a new tab)
As printed in the datasheet, checked November 2026 (the date we compared these figures with the maker's sheet). NA means not published.
AC side
- Rated power
- 4999–5020 kW
- Printed ratings
- 4999, 5020 kW
- Nominal AC voltage
- 690 V
- Grid frequency
- 50/60
DC side
- DC voltage range
- 976–1500 V
- Max DC current
- NA
Performance
- Max efficiency
- 98.94 %
Build
- Type
- NA
- Cooling
- Air
- Ingress protection
- NEMA 3R / IP55
- Operating temperature
- -40–60 °C
- Weight
- 4700 kg
- MV transformer built in
- No
- Communication
- Modbus TCP
Grid functions
- Off-grid / black start
- Yes
- Grid-forming
- Yes
Certification
- Certifications
- UL 1741, CSA 22.2 No.107.1-16, IEC 62109-1, IEC 62109-2, IEC 62477-1, UL 1741 SA & SB, IEEE 1547.1, IEC 62116, G99, VDE 4110-4120-4130, CEI 0-16, NTS 2.1, EN 50549, IEEE 2800
- Size:
- 5000 kW
- Model code:
- FP4997K2, FP4997K4, FP4999K2, FP4999K4, FP5020K2, FP5020K4
- Checked:
- November 2026, against the datasheet
Full datasheet
Every row the maker prints, copied as written, read 2026-11-15.
Overview
- Product
- Freemaq Multi PCSK
- Models
- FP4997K2 / FP4997K4 / FP4999K2 / FP4999K4 / FP5020K2 / FP5020K4
- Description
- OUR PCSK are battery inverters for utility-scale applications.(power-electronics.com)The utility-scale battery inverters. From one independent BESS with PCSK to up to four independent BESS with Multi PCSK.(bucket-software00.s3.eu-west-1.amazonaws.com)
- Power range
- Up to 5360 kVA(power-electronics.com)
- Battery type
- All type of batteries (BMS required)
- Sheet version
- V. 2.0.5 20261022
DC side
- DC voltage range
- 976 V – 1500 VUp to 1500 Vdc(power-electronics.com)
- Max. DC voltage
- 1500 V
- DC voltage windows
- Nine different DC voltage windows(power-electronics.com)
- Max. DC current
- FP4997K2: 2588 A; FP4997K4: 1294 A; FP4999K2: 2588 A; FP4999K4: 1294 A; FP5020K2: 2713 A; FP5020K4: 1356 A
- Max. DC continuous current (A)
- FP4997K2: 2740; FP4997K4: 1370; FP4999K2: 2740; FP4999K4: 1370; FP5020K2: 2740; FP5020K4: 1370(bucket-software00.s3.eu-west-1.amazonaws.com)
- Max. DC short-circuit current per input
- 500 kA with a time constant of 1 ms
- DC voltage ripple
- <3%
AC side
- AC output power at 30 °C
- FP4997K2/FP4997K4: 5240 kVA / 4999 kW; FP4999K2: 4999 kVA / kW; FP4999K4: 4999 kVA / kW; FP5020K2/FP5020K4: 5240 kVA / kW
- AC power at 35 °C
- FP4997K2/FP4997K4: 5020 kVA / 4999 kW; FP4999K2: 4999 kVA / kW; FP4999K4: 4999 kVA / kW; FP5020K2/FP5020K4: 5020 kVA / kWFP4997K2/FP4997K4: 5240 kVA / 4999 kW; FP4999K2: 4999 kVA / kW; FP4999K4: 4999 kVA / kW; FP5020K2/FP5020K4: 5020 kVA / kW(bucket-software00.s3.eu-west-1.amazonaws.com)
- AC output power at 40 °C
- 4800 kVA / kW
- AC power at 50 °C
- 4360 kVA / kW
- Nominal AC voltage
- 690 V ±10%
- Grid frequency
- FP4997K2/FP4997K4: 60 Hz; FP4999K2: 50 Hz; FP4999K4: 50 Hz; FP5020K2/FP5020K4: 60 Hz50 / 60 Hz(bucket-software00.s3.eu-west-1.amazonaws.com)
- Max. AC output current at 30 °C
- FP4997K2/FP4997K4: 4384 A; FP4999K2: 4182 A; FP4999K4: 4384 A; FP5020K2/FP5020K4: 4385 A
- Max. AC output current at 30 °C (A)
- FP4997K2/FP4997K4/FP4999K2: 4384; FP4999K4: 4384; FP5020K2/FP5020K4: 4385(bucket-software00.s3.eu-west-1.amazonaws.com)
- Power factor
- 0.5 leading… 0.5 lagging
- Reactive power
- Four quadrant operation
- Current harmonic distortion (THDi)
- <3% per IEEE 519
- Overload capability
- 166% - 100 ms / 150% - 5 s / 120% - 8 s / 110% - 15 s
Off-grid operation
- Grid forming / black start
- Standard
Efficiency
- Max. efficiency
- 98.94%
- European efficiency
- 98.50%
- CEC efficiency
- 98.51%(bucket-software00.s3.eu-west-1.amazonaws.com)
Protection
- DC protection and disconnection
- High-speed fuses, Motorized DC disconnect switches [4]
- AC protection and disconnection
- Circuit breaker
- Overvoltage protection
- Type II for AC and Type I+II for DC
- Ground fault / insulation monitoring
- Insulation monitoring device
- Humidity control
- Active heating
Environment
- Operating temperature
- From -40 °C to +60 °C, >30 °C power derating (optional below -25 ºC)
- Storage temperature
- From -40 °C to +60 °C
- Relative humidity
- From 4% to 100%
- Max. altitude
- 2000 m / >2000 m power derating (max. 4000 m)
- Ingress protection
- NEMA 3R / IP55
- Cooling
- Forced air cooling
Physical
- Footprint dimensions (W × D × H)
- 9.8 x 6.5 x 7.5 ft3.0 x 2.0 x 2.3 m
- Weight
- 10365 lbs4700 kg
Communication
- Communication
- Modbus TCP
Certifications
- Safety standards
- UL 1741 / CSA 22.2 No.107.1-16 / IEC 62109-1 / IEC 62109-2 / IEC 62477-1
- Grid codes
- UL 1741 SA & SB / IEEE 1547.1 / IEC 62116 / G99 / VDE 4110-4120-4130 / CEI 0-16 / NTS 2.1 / EN 50549 / IEEE 2800
- Installation standard
- NEC 2023
Features
- Features
- This product provides advanced grid support capabilities, enabling up to 4* Battery Energy Storage Systems (BESS) to operate simultaneously. It also offers up to nine voltage levels to suit any battery technology. *Only available with Multi PCSK.(power-electronics.com)It offers the advantages of a central inverter with the modularity of string inverters.(power-electronics.com)Designed for easy field maintenance, with up to four FRUs (Field Replaceable Units).(power-electronics.com)It enables higher battery capacity by providing up to four times the short-circuit withstand of single DC input systems. Multiple power references allow for independent control of each BESS. Furthermore, it offers greater availability, as a battery fault only affects the corresponding power modules within the system.(power-electronics.com)Modularity. / Easy maintenance. / Up to 4 independent DC inputs. / Advanced grid support. / Compatible with all battery technologies.Designed for easy on-site replacement, with a safe, reliable, and fast plug-and-play assembly system. Includes up to four FRUs (Field Replaceable Units).(bucket-software00.s3.eu-west-1.amazonaws.com)Enables DC power redistribution when one module fails. Lower energy losses = higher availability and efficiency.(bucket-software00.s3.eu-west-1.amazonaws.com)Capable of operating on any power system, with different modes depending on the application: grid-forming or grid-following.(bucket-software00.s3.eu-west-1.amazonaws.com)The three-level IGBT topology reduces power-stage losses, increases inverter efficiency, and minimizes total harmonic distortion—achieving high efficiency for the lowest levelized cost of energy (LCOE).(bucket-software00.s3.eu-west-1.amazonaws.com)Choose your model based on your specific requirements.(bucket-software00.s3.eu-west-1.amazonaws.com)Maximum power up to 1500 V / Up to 5360 kVA / Ten different voltage DC windows / Full grid support capability / Grid-forming capability / *Up to four independent BESS (*Only Multi PCSK)(bucket-software00.s3.eu-west-1.amazonaws.com)Higher battery capacity thanks to the short-circuit withstand capability of each DC input. Up to four times more than a single input. / Multiple power references allow independent BESS control. / Higher availability since a battery fault will only remove the affected power modules from the system. (Only Multi PCSK)(bucket-software00.s3.eu-west-1.amazonaws.com)
Notes
- Notes
- Values at 1.00·Vac nom and CosPhi=1. Consult Power Electronics for derating curves.Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).Consult Power Electronics for derating curves. In the event of overvoltage in the grid, the minimum DC voltage will vary proportionally with the AC voltage.Battery short circuit disconnection must be done on the battery side.Consult Power Electronics for other applicable standards / grid codes.The content of this document is periodically updated. Power Electronics reserves the right to modify all or part of this document without prior notice.
More PCS from Power Electronics
- Freemaq Multi PCSKBattery inverter with 2–4 separate DC inputs, 480–690 V AC (sheet V. 1.4.5)
- Freemaq Multi PCSKBattery inverter with 2 or 4 separate DC inputs, 720 V AC (Gen3 sheet V. 2.0.5)
- Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 33/34.5 kV, IEC (sheet V. 1.4.4)
- Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 20–34.5 kV, 690 V PCS, IEC (Gen3 sheet V. 2.0.5)
- Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 20–34.5 kV, 720 V PCS, IEC (Gen3 sheet V. 2.0.5)
- Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 33 kV, 690 V PCS, IEC (Gen3 sheet V. 3.0.0, preliminary)
- Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 33 kV, 720 V PCS, IEC (Gen3 sheet V. 3.0.0, preliminary)
- Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 12.47–34.5 kV, UL (sheet V. 1.4.4)
- Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 690 V PCS, UL (Gen3 sheet V. 2.0.4)
- Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 720 V PCS, UL (Gen3 sheet V. 2.0.4)
- Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 690 V PCS, UL (Gen3 sheet V. 3.0.0, preliminary)
- Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 720 V PCS, UL (Gen3 sheet V. 3.0.0, preliminary)
Power Electronics Freemaq Multi PCSK, in short
The Power Electronics Freemaq Multi PCSK is a PCS rated 5000 kW, with max efficiency 98.94%, cooling Air and MV transformer built in: no. Its max efficiency (98.94%) is above the median of the 45 PCS listed (98.7%). 16 other PCS at 5000 kW are listed, from 4 makers. Power Electronics has 25 other PCS on this site.
Same size from other makers: FIMER PVS980-58BC-5000-L, Hitachi Energy India PCS WD4, Kehua BCS4000K~5000K-C-HUD-NP/T4, Power Electronics Freemaq Multi PCSK, Kehua BCS4000K~5000K-C-HUD/T4 Series, Power Electronics Freemaq Multi PCSM IEC · All 5000 kW side by side
Questions about the Power Electronics Freemaq Multi PCSK
- What are the main specifications of the Power Electronics Freemaq Multi PCSK?
- Rated 5000 kW; Max efficiency 98.94%; Cooling Air; MV transformer built in: no. As printed on Power Electronics' datasheet (checked November 2026); the full list is on this page.
- Where can I find the Power Electronics Freemaq Multi PCSK datasheet?
- Power Electronics publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
- What are the alternatives to the Power Electronics Freemaq Multi PCSK?
- Other 5000 kW PCS sold in India include FIMER PVS980-58BC-5000-L, Hitachi Energy India PCS WD4, Kehua BCS4000K~5000K-C-HUD-NP/T4 and Power Electronics Freemaq Multi PCSK. All of them are compared side by side on the 5000 kW page.
- Who makes the Power Electronics Freemaq Multi PCSK?
- Power Electronics, with its head office in Valencia, Spain. It has 26 PCS on this site, including this one.
Spot a wrong or outdated figure? Report a correction and we'll check it against the maker's current sheet.
Values as Power Electronics prints them in the linked datasheet; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with Power Electronics. Product and company names are trademarks of their owners, used only to identify the product.