Power Electronics Freemaq Multi PCSM IEC

Listed A–Z, not ranked · Reviewed November 2026

MV power station with 2 or 4 separate DC inputs, 33/34.5 kV, IEC (sheet V. 1.4.4) · PCS by Power ElectronicsLegacy

As printed in the datasheet, checked November 2026 (the date we compared these figures with the maker's sheet). NA means not published.

AC side

Rated power
4010–4200 kW
Printed ratings
4010, 4105, 4200 kW
Nominal AC voltage
NA
Grid frequency
50/60

DC side

DC voltage range
891–1500 V
Max DC current
NA

Performance

Max efficiency
97.8 %

Build

Type
NA
Cooling
Air
Ingress protection
IP55
Operating temperature
-40–60 °C
Weight
14000 kg
MV transformer built in
Yes
Communication
Modbus TCP

Grid functions

Off-grid / black start
Not stated
Grid-forming
Not stated

Certification

Certifications
IEC 62109-1, IEC 62109-2, IEC 62477-2
Size:
4010 kW
, 4105 kW
, 4200 kW
Model code:
FP4010MH2, FP4010MH4, FP4105MH2, FP4105MH4, FP4200MH2, FP4200MH4, FP4203MH2, FP4203MH4, FP4207MH2, FP4207MH4
Checked:
November 2026, against the datasheet

Note

MV power station (PCS with MV transformer); figures are for the station.

Full datasheet

Every row the maker prints, copied as written, read 2026-11-15.

Overview

Models
FP4010MH2, FP4010MH4, FP4105MH2, FP4105MH4, FP4200MH2, FP4200MH4, FP4203MH2, FP4203MH4, FP4207MH2, FP4207MH4
Description
Our most powerful MV battery inverter for utility-scale applications. Designed to operate in any environment and compatible with all battery technologies.(power-electronics.com)
Power range
Up to 5360 kVA(power-electronics.com)
Battery type
All type of batteries (BMS required)

DC side

DC voltage range
FP4010MH2, FP4010MH4: 891 V - 1500 V; FP4105MH2, FP4105MH4: 913 V - 1500 V; FP4200MH2, FP4200MH4, FP4203MH2, FP4203MH4, FP4207MH2, FP4207MH4: 934 V - 1500 VUp to 1500 Vdc(power-electronics.com)
Max. DC voltage
1500 V
DC voltage windows
Three different DC voltage windows(power-electronics.com)Five different DC voltage windows(bucket-software00.s3.eu-west-1.amazonaws.com)
Max. DC continuous current per input (A)
FP4010MH2, FP4105MH2, FP4200MH2, FP4203MH2, FP4207MH2: 2295; FP4010MH4, FP4105MH4, FP4200MH4, FP4203MH4, FP4207MH4: 1148
Max. DC short-circuit current per input
500 kA with a time constant of 1 ms
DC voltage ripple
<3%
Number of DC inputs
FP4010MH2, FP4105MH2, FP4200MH2, FP4203MH2, FP4207MH2: 2; FP4010MH4, FP4105MH4, FP4200MH4, FP4203MH4, FP4207MH4: 4

AC side

AC output power at 40 °C (kVA/kW)
FP4010MH2, FP4010MH4: 4010; FP4105MH2, FP4105MH4: 4105; FP4200MH2, FP4200MH4, FP4203MH2, FP4203MH4, FP4207MH2, FP4207MH4: 4200
AC output power at 50 °C (kVA/kW)
FP4010MH2, FP4010MH4: 3720; FP4105MH2, FP4105MH4: 3810; FP4200MH2, FP4200MH4, FP4203MH2, FP4203MH4, FP4207MH2, FP4207MH4: 3900
Operating grid voltage (kV)
FP4010MH2, FP4010MH4, FP4105MH2, FP4105MH4, FP4200MH2, FP4200MH4: 34.5 kV ±10%; FP4203MH2, FP4203MH4, FP4207MH2, FP4207MH4: 33 kV ±10%
Grid frequency
FP4010MH2, FP4010MH4, FP4105MH2, FP4105MH4, FP4200MH2, FP4200MH4: 60 Hz; FP4203MH2, FP4203MH4, FP4207MH2, FP4207MH4: 50 Hz
Power factor
0.5 leading … 0.5 lagging
Reactive power
Four quadrant operation
Current harmonic distortion (THDi)
<3% per IEEE 519
Overload capability
166% - 100 ms / 150% - 5 s / 120% - 8 s / 110% - 15 s

Efficiency

Max. efficiency (preliminary)
FP4010MH2, FP4010MH4: 97.75% including MV transformer; FP4105MH2, FP4105MH4: 97.76% including MV transformer; FP4200MH2, FP4200MH4, FP4203MH2, FP4203MH4, FP4207MH2, FP4207MH4: 97.80% including MV transformer
European efficiency (preliminary)
FP4010MH2, FP4010MH4: 97.48% including MV transformer; FP4105MH2, FP4105MH4: 97.50% including MV transformer; FP4200MH2, FP4200MH4, FP4203MH2, FP4203MH4, FP4207MH2, FP4207MH4: 97.51% including MV transformer

Protection

DC protection and disconnection
High-speed fuses, Motorized DC disconnect switches
AC protection and disconnection
36 kV MV switchgear (2L+V)
Overvoltage protection
Type II for AC and Type I+II for DC
Ground fault / insulation monitoring
Insulation monitoring device
Humidity control
Active heating

Environment

Operating temperature
From -40 °C to +60 °C, >40 °C power deratingUp to 50°C(power-electronics.com)
Storage temperature
From -40 °C to +60 °C
Relative humidity
From 4% to 100%
Max. altitude
FP4010MH2, FP4010MH4, FP4105MH2, FP4105MH4, FP4200MH2, FP4200MH4: 2000 m; FP4203MH2, FP4203MH4: 1000 m; FP4207MH2, FP4207MH4: 2000 m
Ingress protection
IP55
Cooling
Forced air cooling

Physical

Dimensions W × D × H (m)
6.5 x 2.0 x 2.3
Dimensions W × D × H (ft)
21.3 x 6.5 x 7.5
Weight
3086514000

Communication

Communication
Modbus TCP
Display / user interface
Standard
Power plant controller
Optional. Third party SCADA systems supported.

Certifications

Safety standards
IEC 62109-1 / IEC 62109-2 / IEC 62477-2

Features

Features
Easy maintenance.Integrated MV solution in the same enclosure.Up to 4 independent DC inputs.Advanced grid support.Compatible with all battery technologies.Our PCSM and Multi PCSM feature a robust and durable design, advanced grid support capabilities, and allow the connection of up to four* independent BESS units. *Only available with Multi PCSM.(power-electronics.com)Designed for easy field installation, with a safe, reliable, and efficient Plug & Play assembly system. Choose the model that best fits your requirements.(power-electronics.com)Housed within a single enclosure, it provides a turnkey storage solution that simplifies installation design.(power-electronics.com)The forced air cooling system provides a constant flow of clean air inside the equipment, without the need for liquid cooling.(power-electronics.com)It enables DC power redistribution in the event of module failure, reducing energy losses and improving availability and performance.(power-electronics.com)Capable of operating on any power system, with different operation modes depending on the application: grid forming or grid following.(power-electronics.com)The three-level IGBT topology reduces power-stage losses, increases inverter efficiency, and minimizes total harmonic distortion—achieving high efficiency for the lowest levelized cost of energy (LCOE).(bucket-software00.s3.eu-west-1.amazonaws.com)Designed for easy on-site replacement, with a safe, reliable, and fast plug-and-play assembly system. Includes 4 FRUs (Field Replaceable Units).(bucket-software00.s3.eu-west-1.amazonaws.com)

More PCS from Power Electronics

  • Freemaq Multi PCSKBattery inverter with 2–4 separate DC inputs, 480–690 V AC (sheet V. 1.4.5)
  • Freemaq Multi PCSKBattery inverter with 2 or 4 separate DC inputs, 690 V AC (Gen3 sheet V. 2.0.5)
  • Freemaq Multi PCSKBattery inverter with 2 or 4 separate DC inputs, 720 V AC (Gen3 sheet V. 2.0.5)
  • Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 20–34.5 kV, 690 V PCS, IEC (Gen3 sheet V. 2.0.5)
  • Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 20–34.5 kV, 720 V PCS, IEC (Gen3 sheet V. 2.0.5)
  • Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 33 kV, 690 V PCS, IEC (Gen3 sheet V. 3.0.0, preliminary)
  • Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 33 kV, 720 V PCS, IEC (Gen3 sheet V. 3.0.0, preliminary)
  • Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 12.47–34.5 kV, UL (sheet V. 1.4.4)
  • Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 690 V PCS, UL (Gen3 sheet V. 2.0.4)
  • Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 720 V PCS, UL (Gen3 sheet V. 2.0.4)
  • Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 690 V PCS, UL (Gen3 sheet V. 3.0.0, preliminary)
  • Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 720 V PCS, UL (Gen3 sheet V. 3.0.0, preliminary)
All 26 on the Power Electronics profile

Power Electronics Freemaq Multi PCSM IEC, in short

The Power Electronics Freemaq Multi PCSM IEC is a PCS rated 4010 kW, with max efficiency 97.8%, cooling Air and MV transformer built in. Its max efficiency (97.8%) is below the median of the 45 PCS listed (98.7%). Power Electronics has 25 other PCS on this site.

Questions about the Power Electronics Freemaq Multi PCSM IEC

What are the main specifications of the Power Electronics Freemaq Multi PCSM IEC?
Rated 4010 kW; Max efficiency 97.8%; Cooling Air; MV transformer built in. As printed on Power Electronics' datasheet (checked November 2026); the full list is on this page.
Where can I find the Power Electronics Freemaq Multi PCSM IEC datasheet?
Power Electronics publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
Who makes the Power Electronics Freemaq Multi PCSM IEC?
Power Electronics, with its head office in Valencia, Spain. It has 26 PCS on this site, including this one.

Spot a wrong or outdated figure? Report a correction and we'll check it against the maker's current sheet.

Values as Power Electronics prints them in the linked datasheet; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with Power Electronics. Product and company names are trademarks of their owners, used only to identify the product.

Not sure what to buy? Ask us what's compatible and what size fits your site.