Listed A–Z, not ranked · Reviewed November 2026
MV power station with 2 or 4 separate DC inputs, 12.47–34.5 kV, UL (sheet V. 1.4.4) · PCS by Power ElectronicsLegacy
Specifications
Datasheet on bucket-software00.s3.amazonaws.com(opens in a new tab)Product pageon power-electronics.com (opens in a new tab)
As printed in the datasheet, checked November 2026 (the date we compared these figures with the maker's sheet). NA means not published.
AC side
- Rated power
- 4010–4200 kW
- Printed ratings
- 4010, 4105, 4200 kW
- Nominal AC voltage
- NA
- Grid frequency
- 60
DC side
- DC voltage range
- 891–1500 V
- Max DC current
- NA
Performance
- Max efficiency
- 98 %
Build
- Type
- NA
- Cooling
- Air
- Ingress protection
- NEMA 3R
- Operating temperature
- -40–60 °C
- Weight
- 14000 kg
- MV transformer built in
- Yes
- Communication
- Modbus TCP
Grid functions
- Off-grid / black start
- Not stated
- Grid-forming
- Not stated
Certification
- Certifications
- UL 1741, CSA 22.2 No.107.1-16, UL 1741 SA & SB, RULE 21, RULE 14H, IEEE 1547.1
- Size:
- 4010 kW
- , 4105 kW
- , 4200 kW
- Model code:
- FP4010M2, FP4010M4, FP4105M2, FP4105M4, FP4200M2, FP4200M4, FP4201M2, FP4201M4, FP4204M2, FP4204M4
- Checked:
- November 2026, against the datasheet
Note
MV power station (PCS with MV transformer); figures are for the station.
Full datasheet
Every row the maker prints, copied as written, read 2026-11-15.
Overview
- Models
- FP4010M2, FP4010M4, FP4105M2, FP4105M4, FP4200M2, FP4200M4, FP4201M2, FP4201M4, FP4204M2, FP4204M4
- Description
- Our most powerful MV battery inverter for utility-scale applications. Designed to operate in any environment and compatible with all battery technologies.(power-electronics.com)
- Power range
- Up to 5360 kVA(power-electronics.com)
- Battery type
- All type of batteries (BMS required)
DC side
- DC voltage range
- FP4010M2/M4: 891 V - 1500 V; FP4105M2/M4: 913 V - 1500 V; FP4200M2/M4, FP4201M2/M4, FP4204M2/M4: 934 V - 1500 VUp to 1500 Vdc(power-electronics.com)
- Max. DC voltage
- 1500 V
- DC voltage windows
- Three different DC voltage windows(power-electronics.com)
- Max. DC continuous current per input (A)
- M2 references (FP4010M2, FP4105M2, FP4200M2, FP4201M2, FP4204M2): 2295; M4 references (FP4010M4, FP4105M4, FP4200M4, FP4201M4, FP4204M4): 1148
- Max. DC short-circuit current per input
- 500 kA with a time constant of 1 ms
- DC voltage ripple
- < 3%
- Number of DC inputs
- M2 references: 2; M4 references: 4
AC side
- AC output power at 40 °C (kVA/kW)
- FP4010M2: 4010; FP4010M4: 4010; FP4105M2: 4105; FP4105M4: 4105; FP4200M2: 4200; FP4200M4: 4200; FP4201M2: 4200; FP4201M4: 4200; FP4204M2: 4200; FP4204M4: 4200
- AC output power at 50 °C (kVA/kW)
- FP4010M2: 3720; FP4010M4: 3720; FP4105M2: 3810; FP4105M4: 3810; FP4200M2: 3900; FP4200M4: 3900; FP4201M2: 3900; FP4201M4: 3900; FP4204M2: 3900; FP4204M4: 3900
- Operating grid voltage (kV)
- FP4010M2/M4: 34.5 kV ±10%; FP4105M2/M4: 34.5 kV ±10%; FP4200M2/M4: 34.5 kV ±10%; FP4201M2/M4: 13.8 kV ±10%; FP4204M2/M4: 12.47 kV ±10%
- Grid frequency
- 60 Hz
- Power factor
- 0.5 leading … 0.5 lagging
- Reactive power
- Four quadrant operation
- Current harmonic distortion (THDi)
- < 3% per IEEE519
- Overload capability
- 166% - 100 ms / 150% - 5 s / 120% - 8 s / 110% - 15 s
Efficiency
- Max. efficiency
- FP4010M2/M4: 97.91% including MV transformer; FP4105M2/M4: 97.93% including MV transformer; FP4200M2/M4, FP4201M2/M4, FP4204M2/M4: 98.00% including MV transformer
- CEC efficiency
- FP4010M2/M4: 97.49% including MV transformer; FP4105M2/M4: 97.50% including MV transformer; FP4200M2/M4, FP4201M2/M4, FP4204M2/M4: 97.53% including MV transformer
Protection
- DC protection and disconnection
- High-speed fuses, Motorized DC disconnect switches
- AC protection and disconnection
- FP4010M2/M4, FP4105M2/M4, FP4200M2/M4: 38 kV MV switchgear (V); FP4201M2/M4, FP4204M2/M4: 15.5 kV SF6 Free MV switchgear (V)
- Overvoltage protection
- Type II for AC and Type I+II for DC
- Ground fault / insulation monitoring
- Insulation monitoring device
- Humidity control
- Active heating
Environment
- Operating temperature
- From -40 °C to +60 °C, >40 °C power deratingUp to 50°C(power-electronics.com)
- Storage temperature
- From -40 °C to +60 °C
- Relative humidity
- From 4% to 100%
- Max. altitude
- 2000 m
- Ingress protection
- NEMA 3R
- Cooling
- Forced air cooling
Physical
- Dimensions W × D × H (m)
- 6.5 x 2.0 x 2.3
- Dimensions W × D × H (ft)
- 21.3 x 6.5 x 7.5
- Weight
- 3086514000
Communication
- Communication
- Modbus TCP
- Display / user interface
- Standard
- Power plant controller
- Optional. Third party SCADA systems supported.
Certifications
- Safety standards
- UL 1741 / CSA 22.2 No.107.1-16
- Grid codes
- UL 1741 SA & SB / RULE 21 / RULE 14H / IEEE 1547.1:2020
- Installation standard
- NEC 2023
Features
- Features
- Easy maintenance.Integrated MV solution in the same enclosure.Up to 4 independent DC inputs.Advanced grid support.Compatible with all battery technologies.Our PCSM and Multi PCSM feature a robust and durable design, advanced grid support capabilities, and allow the connection of up to four* independent BESS units. (*Only available with Multi PCSM.)(power-electronics.com)Designed for easy field installation, with a safe, reliable, and efficient Plug & Play assembly system. Choose the model that best fits your requirements.(power-electronics.com)Housed within a single enclosure, it provides a turnkey storage solution that simplifies installation design.(power-electronics.com)The forced air cooling system provides a constant flow of clean air inside the equipment, without the need for liquid cooling.(power-electronics.com)It enables DC power redistribution in the event of module failure, reducing energy losses and improving availability and performance.(power-electronics.com)Capable of operating on any power system, with different operation modes depending on the application: grid forming or grid following.(power-electronics.com)
More PCS from Power Electronics
- Freemaq Multi PCSKBattery inverter with 2–4 separate DC inputs, 480–690 V AC (sheet V. 1.4.5)
- Freemaq Multi PCSKBattery inverter with 2 or 4 separate DC inputs, 690 V AC (Gen3 sheet V. 2.0.5)
- Freemaq Multi PCSKBattery inverter with 2 or 4 separate DC inputs, 720 V AC (Gen3 sheet V. 2.0.5)
- Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 33/34.5 kV, IEC (sheet V. 1.4.4)
- Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 20–34.5 kV, 690 V PCS, IEC (Gen3 sheet V. 2.0.5)
- Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 20–34.5 kV, 720 V PCS, IEC (Gen3 sheet V. 2.0.5)
- Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 33 kV, 690 V PCS, IEC (Gen3 sheet V. 3.0.0, preliminary)
- Freemaq Multi PCSM IECMV power station with 2 or 4 separate DC inputs, 33 kV, 720 V PCS, IEC (Gen3 sheet V. 3.0.0, preliminary)
- Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 690 V PCS, UL (Gen3 sheet V. 2.0.4)
- Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 720 V PCS, UL (Gen3 sheet V. 2.0.4)
- Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 690 V PCS, UL (Gen3 sheet V. 3.0.0, preliminary)
- Freemaq Multi PCSM ULMV power station with 2 or 4 separate DC inputs, 34.5 kV, 720 V PCS, UL (Gen3 sheet V. 3.0.0, preliminary)
Power Electronics Freemaq Multi PCSM UL, in short
The Power Electronics Freemaq Multi PCSM UL is a PCS rated 4010 kW, with max efficiency 98%, cooling Air and MV transformer built in. Its max efficiency (98%) is below the median of the 45 PCS listed (98.7%). Power Electronics has 25 other PCS on this site.
Questions about the Power Electronics Freemaq Multi PCSM UL
- What are the main specifications of the Power Electronics Freemaq Multi PCSM UL?
- Rated 4010 kW; Max efficiency 98%; Cooling Air; MV transformer built in. As printed on Power Electronics' datasheet (checked November 2026); the full list is on this page.
- Where can I find the Power Electronics Freemaq Multi PCSM UL datasheet?
- Power Electronics publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
- Who makes the Power Electronics Freemaq Multi PCSM UL?
- Power Electronics, with its head office in Valencia, Spain. It has 26 PCS on this site, including this one.
Spot a wrong or outdated figure? Report a correction and we'll check it against the maker's current sheet.
Values as Power Electronics prints them in the linked datasheet; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with Power Electronics. Product and company names are trademarks of their owners, used only to identify the product.
