Cold storage ke liye battery: kaun sa compressor, kaun se mahine, kitna diesel

Mid-February se aalu aana shuru hota hai, chamber ka temperature girane ke liye dono compressor full chalte hain, aur phir late March se October tak ek compressor store ko hold karta hai jabki light aati-jaati rehti hai. Yeh page battery ko isi saal ke hisaab se size karta hai, aapki apni bhasha mein: tonne, chamber, compressor aur diesel ke litre.

16 November 2026 ko Ingro Energy ki project team ne check kiya

Seedha jawab

  • Battery holding ke mahino ke hisaab se lijiye, loading ke mahine ke hisaab se nahi. National Horticulture Board ke 5,000 tonne aalu store ke type design mein loading aur pull-down ke waqt plant lagbhag 125 kW leta hai, lekin holding mein sirf lagbhag 60 kW, ek compressor par.
  • DG ki ek unit sirf diesel mein lagbhag ₹30 ki padti hai; grid ki unit battery mein bhar kar lagbhag ₹11 ki. Battery jo bhi unit DG se hata deti hai, us par lagbhag ₹19 bachte hain.
  • Battery ammonia compressor start kar sakti hai, lekin tabhi jab inverter us motor ke starting current ke hisaab se chuna gaya ho. Yeh likhit mein maangiye.
  • Loading aur lambe cut ke liye DG rakhiye. Agar DG zyadatar ek loading ke mahine mein hi chalta hai, ya store saal ke zyada hisse khaali rehta hai, to battery ka paisa wasool nahi hoga.
Apne diesel se hisaab lagaiye

Battery ka size aapka season tay karta hai, connected load nahi

Aalu ke store mein load ke teen bilkul alag daur hote hain. National Horticulture Board ka 5,000 tonne aalu store ka type design (chaar chamber, ammonia plant) inhe neeche jaisa nikaalta hai. Aapka store thoda alag hoga, lekin pattern yahi rahega.

DaurKya chalta haiPlant ka loadRoz ki unit
Loading aur pull-down (design mein 15 Feb se 15 March)Do compressor, do condenser pump, saare cooler fan full speed parlagbhag 125 kWlagbhag 2,000
Holding (October ke ant tak)Ek compressor, ek condenser pump, VFD se dheeme fanlagbhag 60 kWlagbhag 870
Lean (store ka kuch hissa khaali)Ek compressor aadhi capacity parlagbhag 39 kWlagbhag 560

Loading lagbhag ek mahina chalti hai; holding saat-aath mahine. Holding load ke hisaab se li gayi battery un mahino mein roz kaam karti hai. Loading peak ke hisaab se li to dugni mehngi padegi aur baaki saal aadhi khaali baithegi. Punjab mein store aam taur par November ke ant tak khaali ho jaate hain, aur zyadatar cold store saal mein lagbhag aadhe samay khaali rehte hain.

Standard khud kehta hai ki pull-down ke liye ek bada DG aur holding ke liye ek chhota DG rakha ja sakta hai. Chhote DG ka kaam battery le sakti hai; bada DG loading ke liye rahega.

Aapke plant room mein kya chal raha hai

NHB standard ke design ammonia par hain, aur standard ise is kaam ke liye sabse achha refrigerant maanta hai. Uska aam set hai teen reciprocating multi-cylinder compressor, har ek 50% capacity ka, ek standby mein, saath mein atmospheric ya evaporative condenser aur har chamber mein chhat se latke air cooling unit. 5,000 tonne ke design mein har compressor par 55 kW ki motor hai. Freon (HFC) plant mein scroll, reciprocating ya screw compressor hote hain, alag condensing unit ya rack ke roop mein. Controlled-atmosphere (CA) seb ke store mein nitrogen generator aur ethylene scrubber bhi chalte hain.

Battery ke inverter ko inme se ek compressor motor start karni hai. Motor start hote waqt kuch second ke liye running current ka kai guna current kheenchti hai; sirf running load ke hisaab se chuna inverter usi pal trip ho jaata hai. Start kitna bhaari hoga, yeh teen cheezein tay karti hain:

  • Unloaded start. Standard ammonia compressor mein capacity control aur unloaded start maangta hai, jisse start ka zor kam hota hai. Check kijiye ki aapke compressor mein yeh hai aur kaam karta hai.
  • Compressor par soft starter ya VFD. Dono starting current kam karte hain; VFD se compressor holding load ke hisaab se chal bhi sakta hai.
  • Ek baar mein ek start. Doosra compressor aur condenser pump pehle wale ke kuch second baad chalein, kabhi ek saath nahi.

Light jaane par aapka cold storage kaun chalata hai

Light aa rahi hai
GridPlant chala raha hai
BatteryGrid ya solar se charge ho rahi hai
DG setBand. Diesel nahi jal raha
Aapka cold storageEk compressor, condenser pump, cooler fan
Light gayi
GridSupply nahi
BatteryApne aap load leti hai aur compressor chalta rehta hai
DG setTabhi chalta hai jab cut battery se lamba ho, aur loading ke mahine mein
Aapka cold storageEk compressor, condenser pump, cooler fan

Bhara hua teer dikhata hai ki load kaun utha raha hai. Dotted teer backup mein khade DG ka hai.

Darwaze band hon to aalu ka chamber kitni der tikta hai

Jitna log sochte hain usse kam. Aalu store mein bhi zinda rehta hai aur saans leta rehta hai, aur isse garmi nikalti hai. NHB design mein holding ke mahino ki cooling ka lagbhag aadha hissa aalu ki apni garmi ka hai. Plant band ho to saare darwaze band hone par bhi chamber garam hota jaata hai.

Standard kehta hai ki har chamber apne set point se 1°C ke andar rahe: seed aalu ke liye lagbhag 3°C, table aalu ke liye 4°C, ya processing aalu ke liye lagbhag 11°C. Ek ghante ka cut zyada nuksaan nahi karta. Garmi ke din kai ghante ka cut chamber ko is daayre se bahar le ja sakta hai. Set point quality se juda hai: garam rakha aalu jaldi ankurit hota hai, isliye 11°C par processing aalu ke liye sprout suppressor lagta hai, aur thanda rakha aalu meetha ho jaata hai.

Band chamber mein aalu se nikli carbon dioxide bhi badhti hai. Standard holding mein ise 2,000 ppm tak rakhta hai, isiliye store darwaze aur khidkiyan khol kar chamber ko hawa dete hain. Cut ke dauraan darwaze aur khidkiyan band rakhiye, aur plant wapas chalne tak hawa mat dijiye.

Battery size karwane se pehle apna chamber naapiye. Agle cut mein darwaze band rakh kar har 30 minute par chamber ka temperature likhiye. Woh kitni tezi se chadhta hai, isse pata chalega ki plant kitne minute band reh sakta hai, aur kitni battery chahiye.

Battery kaun sa load chalaye

  • Chalaye: ek chalta compressor, uska condenser pump, cooler fan (dheeme), overfeed ya liquid pump, aur controls. Yahi holding ka load hai.
  • Zaroorat ho to: alarm, store ka controller aur emergency light. Yeh chhote load hain.
  • Na chalaye: standby compressor, loading mein doosra compressor, grader, lift aur office. Yeh grid ya DG ka intezaar karein.
  • DG sambhale: loading ka mahina aur battery se lamba koi bhi cut. Light jaate hi battery chalti hai, aur DG tabhi start hota hai jab cut battery se lamba ho.

Yeh list sahi banana hi sizing ka sabse bada kaam hai. Battery ke kWh holding load guna aam din ke cut ke ghante se nikalte hain, aur neeche ka calculator isi se kaam karta hai.

Bachat kitni, diesel ke litre mein

DG har litre diesel se lagbhag 3.2 unit banata hai. ₹95 litre par DG ki har unit lagbhag ₹30 ki padti hai, oil, filter aur operator alag. Grid se lagbhag ₹9 par charge hui battery jo leti hai uska lagbhag 85% wapas deti hai, to usse nikli unit lagbhag ₹11 ki padti hai. Holding mein halke load par chalta DG litre se kam unit deta hai, jisse battery aur fayde ki dikhti hai.

Ek udaharan, kisi asli store ka nahi: holding ke mahino mein aalu store, plant lagbhag 50 kW le raha hai, light roz lagbhag 6 ghante jaati hai (May 2026 mein UP ki bijli company ko gaon mein 18 ghante supply dene ko kaha gaya tha), aur 8 mahine har cut DG sambhalta hai. Yani DG se roz lagbhag 299 unit, ya mahine mein lagbhag 2,800 litre diesel (₹2.7 lakh). Lagbhag 340 kWh ki battery ek charge mein woh din nikaal deti hai. Calculator ke hi hisaab se yeh mahine mein lagbhag ₹1.7 lakh, saal mein ₹14 lakh bachati hai, lagwane mein lagbhag ₹68 se 102 lakh lagte hain, aur paisa lagbhag 5.0 se 7.5 saal mein wasool hota hai.

Apne litre daaliye: sirf holding ke mahino ka diesel giniye, loading ka mahina litre mein mat jodiye. Tabhi sahi figure aayega.

Apne diesel se hisaab lagaiye

Holding ke mahino ke litre daaliye. Jab tak aap check karne ko na kahein, kuch bhi kahin nahi bheja jaata.

Hisaab dekhne ke liye diesel ke litre aur DG ke ghante daaliye.

Yeh hisaab kaise laga
  • DG ek litre diesel se lagbhag 3.2 unit banata hai.
  • Grid ki unit lagbhag ₹9 ki hai, aur battery jo leti hai uska lagbhag 85% wapas deti hai.
  • Battery aisi li gayi hai jo aam din ka poora DG ka kaam ek charge mein utha le.
  • Lagwane ka kharcha 250 kWh se chhoti battery ke liye ₹25,000 se ₹38,000 prati kWh, aur usse badi ke liye ₹20,000 se ₹30,000 prati kWh liya gaya hai, GST alag. Yeh kaam chalau range hai, quotation nahi.
  • DG ki servicing ki bachat, demand charge aur solar nahi gine gaye.
  • Yeh pehla andaaza hai. Price dene se pehle compressor ka starting load aur aapka tariff check kiya jaata hai.

Apne store ka figure paaiye

Naam aur number chhod dijiye. Hum aapke plant ka size, kharcha aur paisa wasool ka samay lekar call karenge.

Apne cold storage ke baare mein bataiye ↓

Cold store mein battery kab nahi leni chahiye

  • DG zyadatar loading ke mahine mein chalta hai. Holding ke cut chhote ya kabhi-kabhar hain, to bachane ko diesel hi kam bachta hai.
  • Store mahino khaali rehta hai. Bachat sirf plant chalne ke mahino mein hoti hai, to paisa wasool hone mein der lagti hai.
  • Season mein feeder din ka zyada hissa band rehta hai. Do cut ke beech battery charge nahi ho paati, aur DG chalta hi hai. Solar ke saath chhoti battery behtar baithti hai.
  • Insulation ya darwaze kharab hone se chamber jaldi garam hota hai. Pehle woh theek kijiye: NHB ki capital investment subsidy mein insulation aur refrigeration ka modernisation bhi aata hai.
  • Aapke compressor bijli ki motor par nahi, diesel engine par chalte hain. Unke liye battery kuch nahi karti.

Khet ke paas chhote cold room ke liye sarkar ka solar cold storage ka draft standard (MNRE, February 2025) backup ke liye battery nahi, thermal (barf) storage rakhta hai. 5,000 tonne ke store ke liye battery ya DG hi kaam ka backup hai.

Store ki chhat par solar

Cold store ki chhat badi hoti hai aur plant poori garmi chalta hai, jab solar sabse zyada banata hai. October 2026 ki report ke mutabik Kotulpur, Bankura (West Bengal) ke ek aalu cold store ne chhat par 250 kW panel lagaye. Uski khapat saal mein lagbhag 120 MWh thi, aur chhat kitna wazan le sakti hai, isse mounting structure tay hua. Panel ki planning se pehle chhat check karwaiye.

Aam grid-tied solar light jaane par band ho jaata hai. Battery ho to din ke cut mein bhi panel compressor chalate rehte hain aur battery charge karte hain. Central cold-chain scheme ke project datasheet mein solar PV, battery capacity aur backup ghante ki line pehle se hai.

Kharcha aur battery ki umar, thode mein

Is size ka lagaya hua system battery ke har kWh par lagbhag ₹20,000 se ₹35,000 ka padta hai, GST alag, jismein inverter, aapke maujooda DG changeover se juda changeover panel aur civil kaam shaamil hai. Neeche diye kharche wale guide aur battery-ya-DG wale guide mein poori baat hai.

Yeh battery lithium iron phosphate (LFP) cell ki hoti hain, warranty saal ya cycle mein aur aakhir mein bachi capacity ke saath. Garmi se umar ghatti hai, isliye cabinet thandi, hawadaar jagah rakhiye, condenser se door aur ammonia plant room ke bahar.

Sign karne se pehle kya poochein

  • Kya yeh mera sabse bada compressor, itne kW aur is starter wala, sirf battery par start karegi? Likhit mein.
  • Holding ke mahino mein kaun sa load chalayegi, aur kitne ghante?
  • Light jaane par switch itna jaldi hoga ki compressor low oil pressure ya kam voltage par trip na ho?
  • Mere maujooda DG changeover se kaise judegi, taaki grid, battery aur DG sahi kram mein apne aap sambhalein?
  • Cabinet kahan rakhenge, aur ammonia plant room aur condenser ki garmi se kaise door rahega?
  • Warranty kitne saal aur kitne cycle ki hai, aur February-March mein loading ke beech band ho jaaye to kaun aayega?

Aage padhiye aur saamaan dekhiye

Cold storage malik jo poochte hain

Kya battery loading ka season utha sakti hai?

Utha sakti hai, par shayad hi kabhi fayde ka sauda hai. Loading aur pull-down mein holding ka lagbhag dugna load sirf lagbhag ek mahine ke liye chahiye. Battery holding ke hisaab se lijiye aur loading DG ko sambhalne dijiye.

Kya battery mera ammonia compressor start karegi?

Haan, agar inverter us compressor ke starting current ke hisaab se chuna gaya ho, compressor unloaded start ho, aur usi pal kuch aur start na ho. Soft starter ya VFD ho to aur aasaan.

Aalu ka chamber bina light ke kitni der tik sakta hai?

Yeh insulation, bahar ki garmi aur chamber kitna bhara hai, is par nirbhar hai. Aalu store mein garmi deta hai, isliye darwaze band hone par bhi chamber garam hota hai. Apne store ke liye agle cut mein har 30 minute par temperature likhiye.

Store khaali ho to battery ka kya karein?

Woh cut mein office, light aur yard chalati hai, aur charge rakhi jaati hai. Bachat plant chalne ke mahino mein hoti hai, isiliye calculator wahi mahine poochta hai.

Kya NHB subsidy mein battery aati hai?

NHB capital investment subsidy ke page par naye store aur insulation-refrigeration ka modernisation likha hai. Battery ka zikr nahi hai. Cold-chain project datasheet mein battery backup ke saath solar PV ki line hai. Bharosa karne se pehle bank ya consultant se poochiye.

DG ki unit aur battery ki unit mein kitna fark hai?

₹95 litre aur litre se lagbhag 3.2 unit par DG ki unit sirf diesel mein lagbhag ₹30 ki padti hai. ₹9 ki grid unit battery mein bhar kar lagbhag ₹11 ki padti hai.

Sources

  1. NHB: Technical Standards for Cold Storage Type 01 (potato, onion), NHB-CS-Type 01-2010, notified 25 Feb 2010
  2. NHB: Technical Standards for Controlled Atmosphere stores, NHB-CS-Type 03-2010
  3. NHB: Capital Investment Subsidy for cold storages
  4. NCCD: Component datasheets for cold-chain projects (MIDH Appendix II), December 2014
  5. Down To Earth: Punjab's cold storage owners struggle to stay in business, 14 Feb 2019
  6. Mercom India: West Bengal cold storage operator turns to solar, 1 Oct 2026
  7. Indian Infrastructure: MNRE draft guidelines for solar cold storage with thermal storage backup, 17 Feb 2025
  8. India TV: UPPCL told to ensure 18 hours of rural supply, 23 May 2026

In sites ko battery storage se fayda hua

Alag-alag sites, ek hi baat: apni solar aur green bijli zyada istemaal kijiye, bijli ka bill ghataiye, aur grid saath na de tab bhi kaam chalta rahe.

Apne cold storage ke baare mein bataiye

Jo pata hai bhej dijiye. Ingro ka engineer aapke store ke liye kaun sa load chalana hai, battery ka size, kharcha aur paisa wasool hone ka samay nikaalega, muft.

Aage kya hoga: ek working day ke andar hum phone ya WhatsApp par jawab denge. Abhi site visit ki zaroorat nahi, aur kuch dena nahi hai.

Chhat par solar