Listed A–Z, not ranked · Reviewed November 2026
Specifications
As printed in the spec page, checked November 2026 (the date we compared these figures with the maker's sheet). NA means not published.
AC side
- Rated power
- 100–200 kW
- Printed ratings
- 100, 200 kW
- Nominal AC voltage
- 400–690 V
- Grid frequency
- 50/60
DC side
- DC voltage range
- 600–1450 V
- Max DC current
- NA
Performance
- Max efficiency
- NA
Build
- Type
- Modular
- Cooling
- Air
- Ingress protection
- IP66
- Operating temperature
- -35–60 °C
- Weight
- NA
- MV transformer built in
- No
- Communication
- RS485, CAN, Ethernet, Modbus RTU, Modbus TCP
Grid functions
- Off-grid / black start
- Yes
- Grid-forming
- Not stated
Certification
- Certifications
- IEC/EN 62477-1, EN IEC 61000-6-2/4, EN 61000-3-12, EN IEC 61000-3-11, EN 50549-1, NC RfG, VDE-AR-N 4105
- Model code:
- BCS100K-B-HM X2, BCS200K-B-HM X2
- Checked:
- November 2026, against the spec page
Full datasheet
Every row the maker prints, copied as written, read 2026-11-15.
Overview
- Product
- Modular Energy Storage Converter (DC-AC)(digitalenergy.kehua.com)
- Series
- BCS100K-B-HM X2 Series(digitalenergy.kehua.com)
- Models
- BCS100K-B-HM X2, BCS200K-B-HM X2
- Topology
- BCS100K-B-HM X2: Non-isolated(digitalenergy.kehua.com)
DC side
- Full-power DC voltage range
- BCS100K-B-HM X2: 600~1000Vdc(digitalenergy.kehua.com)BCS200K-B-HM X2: 1060~1450Vdc
- Max. DC voltage
- BCS100K-B-HM X2: 1000Vdc(digitalenergy.kehua.com)
- Max. DC current
- BCS100K-B-HM X2: 187A(digitalenergy.kehua.com)
- Soft start
- BCS100K-B-HM X2: Yes(digitalenergy.kehua.com)
AC side
- Rated AC power
- BCS100K-B-HM X2: 100kW@45°C(digitalenergy.kehua.com)BCS200K-B-HM X2: 200kW@40°C
- Max. AC power
- BCS100K-B-HM X2: 110kVA(digitalenergy.kehua.com)
- Nominal AC voltage
- BCS100K-B-HM X2: 400Vac 3P3W(digitalenergy.kehua.com)BCS200K-B-HM X2: 690Vac3P3W
- AC voltage range
- BCS100K-B-HM X2: -15%~10% (settable)(digitalenergy.kehua.com)
- Grid frequency
- BCS200K-B-HM X2: 50/60Hz(settable)
- Grid frequency range
- BCS100K-B-HM X2: 50/60Hz (settable)(digitalenergy.kehua.com)
- Max. AC current
- BCS100K-B-HM X2: 158A(digitalenergy.kehua.com)
- Power factor
- BCS100K-B-HM X2: >0.99 (at rated power)(digitalenergy.kehua.com)
- Adjustable power factor
- BCS100K-B-HM X2: 1 (leading)~1 (lagging)(digitalenergy.kehua.com)
- Current harmonic distortion (THDi)
- BCS100K-B-HM X2: <3% (at rated power)(digitalenergy.kehua.com)
Off-grid operation
- Off-grid voltage distortion (THDu)
- BCS100K-B-HM X2: <3% (linear load)(digitalenergy.kehua.com)
Efficiency
- Max. efficiency
- BCS100K-B-HM X2: 98.8%(digitalenergy.kehua.com)
Environment
- Operating temperature
- BCS100K-B-HM X2: -35°C~60°C(digitalenergy.kehua.com)
- Relative humidity
- BCS100K-B-HM X2: 0~100% (no-condensing)(digitalenergy.kehua.com)
- Max. altitude
- BCS100K-B-HM X2: 4000m (>2000m derating)(digitalenergy.kehua.com)
- Ingress protection
- BCS100K-B-HM X2: IP66(digitalenergy.kehua.com)BCS200K-B-HM X2: IP66
- Cooling
- BCS100K-B-HM X2: Intelligent air cooling(digitalenergy.kehua.com)
Physical
- Dimensions (W × H × D)
- BCS100K-B-HM X2: 600x295x900mm(digitalenergy.kehua.com)
- Weight
- BCS100K-B-HM X2: 95kg(digitalenergy.kehua.com)
- Installation
- BCS100K-B-HM X2: Rack-mounted(digitalenergy.kehua.com)
Communication
- Communication
- BCS100K-B-HM X2: Modbus-RTU, Modbus-TCP(digitalenergy.kehua.com)BCS100K-B-HM X2: Ethernet, RS485, CAN(digitalenergy.kehua.com)
- Display / user interface
- BCS100K-B-HM X2: LED(digitalenergy.kehua.com)
Certifications
- Certifications and standards
- BCS100K-B-HM X2: IEC/EN 62477-1, EN IEC 61000-6-2/4, EN 61000-3-12, EN IEC 61000-3-11, EN 50549-1, NC RfG, VDE-AR-N 4105(digitalenergy.kehua.com)
Features
- Features
- NEMA type 4X + C5, designed for extreme environments to provide reliable component protection(digitalenergy.kehua.com)Fast power scheduling(digitalenergy.kehua.com)Independent operation, non master-slave logic(digitalenergy.kehua.com)Non-limited parallel connection in theory(digitalenergy.kehua.com)Up to five units parallel connection in off-grid mode(digitalenergy.kehua.com)Fast plug & play, easy installation(digitalenergy.kehua.com)Modular design, support rack-mounted(digitalenergy.kehua.com)IP66 & C5, adapt to extreme environment, provide reliable component protectionSupport multi-module AC side parallel
Notes
- Notes
- Specification indexes may be subject to changes without further notice.(digitalenergy.kehua.com)
More PCS from Kehua
- BCS1000K~1250K-C-HUD
- BCS1000K~1250K-C-HUD-NP
- BCS12500K~13800K-C-HUD-EP/T4 Series
- BCS1250K~1725K-B-HUD
- BCS2000K~2500K-C-HUD-NP/T2 Series
- BCS2000K~2500K-C-HUD/T2 Series
- BCS2500K~3450K-B-HUD/T Series
- BCS3150K~3500K-C-HUD-EP
- BCS4000K~5000K-C-HUD-NP/T4
- BCS4000K~5000K-C-HUD/T4 Series
- BCS5000K~6900K-B-HUD/T Series
- BCS500K-S-HLC
Kehua BCS100K~200K-B-HM X2, in short
The Kehua BCS100K~200K-B-HM X2 is a PCS rated 100 kW, with cooling Air and MV transformer built in: no. 2 other PCS at 100 kW are listed, from 2 makers. Kehua has 15 other PCS on this site.
Same size from other makers: Delta Electronics India PCS100HV, Ingeteam INGECON SUN STORAGE 100TL · All 100 kW side by side
Questions about the Kehua BCS100K~200K-B-HM X2
- What are the main specifications of the Kehua BCS100K~200K-B-HM X2?
- Rated 100 kW; Cooling Air; MV transformer built in: no. As printed on Kehua's spec page (checked November 2026); the full list is on this page.
- Where can I find the Kehua BCS100K~200K-B-HM X2 spec page?
- Kehua publishes it on its own website, and this page links to it. The figures here were last checked against it in November 2026.
- What are the alternatives to the Kehua BCS100K~200K-B-HM X2?
- Other 100 kW PCS sold in India include Delta Electronics India PCS100HV and Ingeteam INGECON SUN STORAGE 100TL. All of them are compared side by side on the 100 kW page.
- Who makes the Kehua BCS100K~200K-B-HM X2?
- Kehua, with its head office in Xiamen, China. It has 16 PCS on this site, including this one.
Spot a wrong or outdated figure? Report a correction and we'll check it against the maker's current sheet.
Values as Kehua prints them in the linked spec page; NA means it doesn't publish that figure. Nothing here is tested by Ingro Energy, and Ingro Energy is not affiliated with Kehua. Product and company names are trademarks of their owners, used only to identify the product.